ART COOL MINI-SPLIT SINGLE ZONE
ELECTRICAL & REFRIGERATION
Type
ARTCOOL ™
Single Zone
A/C
A/C
A/C
A/C
H/P
H/P
H/P
All equipment single phase.
NOTE: Recommend shielded cable for low voltage wiring.
Please see local electrical codes for proper wire specifications.
Type
ARTCOOL ™
Single Zone
A/C
A/C
A/C
A/C
H/P
H/P
H/P
***Each system is pre-charged with enough refrigerant to charge 25 ft. of line and the interior unit.
NOTE: Systems having the outdoor unit mounted above the indoor unit (e.g. basement
installations) have the following additional requirement:
For systems with maximum elevation of 25 ft. (see Figure A), refrigerant lines must be oil
trapped between 8 ft. and 12 ft. of elevation.
For systems with elevation of greater than 25 ft. Refrigerant lines must be oil trapped at least
every 12 ft. of elevation.
* Each system should have a 6-8 inch inverted trap at the condensing unit if mounted above
indoor unit.
10
•
QUICK REFERENCE
Electrical Specifications
Model
BTUs
LA090CP
9,000
LA120CP
12,000
LA121CPM
11,500
LA180CP
18,000
LA090HP
9,000
LA120HP
12,000
LA121HPM
11,500
Refrigerant Line Specifications***
Model
BTUs
LA090CP
9,000
LA120CP
12,000
LA121CPM
11,500
LA180CP
18,000
LA090HP
9,000
LA120HP
12,000
LA121HP
11,500
Voltage
Rated Amps
Indoor
Outdoor
36V DC
115
36V DC
115
36V DC
115
36V DC
230/208
36V DC
115
36V DC
115
36V DC
115
Wire Size
Minimum AWG
Indoor/Outdoor Connecting Cable Shielded
Pipe Size
Additional
Liquid
Suction
Refrigerant
1/4"
3/8"
0.21 oz./ft.
1/4"
1/2"
0.21 oz./ft.
1/4"
1/2"
0.21 oz./ft.
1/4"
1/2"
0.21 oz./ft.
1/4"
3/8"
0.21 oz./ft.
1/4"
1/2 "
0.21 oz./ft.
1/4"
1/2 "
0.21 oz./ft.
Figure A.
Example: 25 ft. maximum elevation.
MCA*
MOP**
7.2
15
15
9.3
15
20
10.5
15
20
9.8
15
20
7.2
15
20
9.3
15
20
10.5
15
20
*Minimum Circuit Ampacity
**Maximum Overcurrent Protection
14-3
18-4
Max. Pipe
Max.
Length
Elevation
50'
25'
50'
25'
50'
25'
100'
50'
50'
25'
50'
25'
50'
25'
OUTDOOR UNIT
OIL TRAP
INDOOR UNIT
25' maximum
8' minimum
12' maximum