[4] Standard Operation Data
1 Cooling
Items
Indoor
Ambient temp.
Outdoor
Quantity
Indoor unit
Quantity in operation
Model
Main pipe
Piping
Branch pipe
Total piping length
Indoor unit fan notch
Refrigerant volume
Compressor volts / Frequency
Outdoor unit
Indoor unit
BC controller (1, 3)
Oil return
High pressure/Low pressure
BC controller liquid/Intermediate
Discharge (TH1)
Heat exchanger outlet (TH5)
Outdoor
Accumulator
unit
Suction (Comp)
Shell bottom (Comp)
LEV inlet
Indoor
unit
Heat exchanger outlet
Outdoor unit
DB/WB
Q'ty
–
m
5(16.4) 5(16.4) 5(16.4) 5(16.4) 5(16.4) 5(16.4) 5(16.4) 5(16.4)
(Ft)
–
kg(oz)
V
V/Hz
A
Pulse
MPa
(psi)
Inlet
Outlet
˚C
(˚F)
–18–
PURY-80TMU(-A)
26.7˚C(80˚F)/19.4˚C(67˚F)
35˚C(95˚F)
4
4
24
24
20
10
5(16.4)
25(82)
Hi
Hi
Hi
Hi
10 kg(67 oz)
208
230
134/76
134/76
27.4
24.8
330
460
430
300
2000
140
235
2.03/0.49
(294/71)
1.92/1.92
(279/279)
107(225)
50(122)
7(45)
10(50)
12(54)
75(167)
26(79)
15(59)
PURY-100TMU(-A)
26.7˚C(80˚F)/19.4˚C(67˚F)
35˚C(95˚F)
4
4
48
16
24
10
5(16.4)
25(82)
Hi
Hi
Hi
Hi
12 kg(86 oz)
208
230
171/98
171/98
35.2
31.8
410
330
460
300
2000
150
235
1.90/0.39
(276/57)
1.79/1.79
(25/25)
110(230)
47(117)
7(45)
10(50)
12(54)
70(158)
30(86)
15(59)