u Packed valve handling precautions
• Open the valve stem all the way out ; do not try
to open it beyond the stopper.
• Securely tighten the valve stem cap in torque
is as follows :
Gas side (Ø12.7 mm)
Gas side (Ø9.52 mm)
Liquid side (Ø6.35 mm)
Service port
Hexagonal wrench is required.
Fig. 10-4-13
10-4-8. Electrical Work
For the air conditioner that has no power cord,
connect a power cord to it as mentioned below.
3 Units Multi
Model
3M26GAV-E1
Power supply
Maximum running
current
Installation
fuse rating
Power cord
u Wiring connection
1. Remove the side panel and cord clamp from
the outdoor unit.
2. Connect the connecting cable to the terminal
as identified by the matching numbers on the
terminal block of indoor and outdoor unit.
3. Insert the power cord and the connecting
cable fully into the terminal block and secure
it tightly with screws.
4. Insulate the unused cords (conductors) from
water entering in the outdoor unit. Locate
them so that they do not touch any electrical
or metal parts.
5. Secure the power cord and the connecting
cable with the cord clamp.
6. Attach the side panel on the outdoor unit.
50 to 62 N•m (5.0 to 6.2 kgf•m)
33 to 42 N•m (3.3 to 4.2 kgf•m)
14 to 18 N•m (1.4 to 1.8 kgf•m)
14 to 18 N•m (1.4 to 1.8 kgf•m)
4 Units Multi
4M27GAV-E1
~
220 – 240 V
50 Hz
~
220 –
240 V
60 Hz
16.4 A
17.0 A
20 A breaker of fuse
(All types can be used.)
H07 RN-F or 245 IEC 66
(2.5 mm² or more)
3 units (A + B + C) Multi
Terminal block (Connecting cable)
Screw
Connecting cable
(B unit)
Connecting cable
(A unit)
4 units (A + B + C + D) Multi
Terminal block
(Connecting cable)
Screw
Connecting cable
(B unit)
Connecting cable
(A unit)
• Wrong wiring connection may cause some electrical
parts burn out.
• Be sure to use the cord clamps specified positions
with attached to the product.
• Do not damage or scratch the conductive core and
inner insulator of power and inter-connecting cables
when peeling them.
• Be sure to comply with local cords on running the
wire from outdoor unit to indoor unit (size of wire and
wiring method etc.)
• Use the power cord and Inter-connecting cable with
specified thickness, specified type, and protective
devices specified.
u Stripping length power cord and connect-
ing cable
10
L N
10
40
30
Earth line
Power cord
– 89 –
Connecting cable
Power cord
(C unit)
Fig. 10-4-14
Connecting cable
(D unit)
Connecting cable
Power cord
(C unit)
Fig.10-4-15
CAUTION
10
1 2 3
10
30
Earth line
Connecting
cable
Fig. 10-4-16
40