Installation & Operation manual of Jetmaster Vent Free Drop In Fireplace TABLE OF CONTENTS TABLE OF CONTENTS..................2 TECHNICAL DATA .................... 4 DIMENSIONS ................... 4 GAS SPECIFICATIONS ................4 WARNINGS ....................4 INSTALLATION INSTRUCTIONS ................ 5 GENERAL ....................5 CLEARANCE DISTANCES AND MATERIALS ..........5 VENTILATION ...................
Page 3
Installation & Operation manual of Jetmaster Vent Free Drop In Fireplace PLEASE READ ALL RELEVANT INSTRUCTIONS IN THIS MANUAL BEFORE STARTING ANY WORK ON THE UNIT INSTALLERS should read all sections of this manual END USERS: should read all operation and maintenance instructions.
Installation & Operation manual of Jetmaster Vent Free Drop In Fireplace TECHNICAL DATA DIMENSIONS MODEL Width Length Depth DROP IN 1020 360mm 1020mm 160mm GAS SPECIFICATIONS Gas supply MODEL CONSUMPTION CONSUMTION injector pressure Max rate Min rate 43 MJ/hour 28 MJ/hour...
All relevant codes and regulations laid down by the Gas Supply Authorities, Uniform Building Regulations and requirements of Local Municipal Authorities must be adhered to. ONLY a registered gas installer, whom must be accredited by JETMASTER, can perform the installation. All gas installations must comply with the requirements of the national standard SANS 10087-1 Installation and use of this fire must be in accordance with these instructions.
Installation & Operation manual of Jetmaster Vent Free Drop In Fireplace GAS SUPPLY PIPE INSTALLATION The nature of a drop in gas fireplace is such that for most applications it would be necessary to route the gas supply line through the floor. All relevant codes and regulations laid down by the Gas Supply Authorities, Uniform Building Regulations and requirements of Local Municipal Authorities must be adhered to.
Installation & Operation manual of Jetmaster Vent Free Drop In Fireplace STEP 2 Centrally locate the frame, into the hole provided. It is recommended that clear silicone be used to glue the frame onto the surface. This will allow for removal of the frame at a later stage, without damaging of the surface or the frame.
Page 8
Installation & Operation manual of Jetmaster Vent Free Drop In Fireplace Item Description Item Description Valve inlet connection 8mm Copper pipe In line test point STEP 2 Before fitting the rest of the components, it is advisable to verify that the unit functions acceptable.
Installation & Operation manual of Jetmaster Vent Free Drop In Fireplace FITTING FINISHING COMPONENTS STEP 1 The top cover can now be fitted over the steel frame. First connect the Infra Red sensor (IR Sensor) to the outer cover. The connection point is on the inside of one of the short sides of the top cover.
Page 10
Installation & Operation manual of Jetmaster Vent Free Drop In Fireplace Now, drop the cover over the steel frame. The inner flanges of the cover must be located on the outside of the steel ribs of the frame, Secure the top cover in place using M4 bolts and nuts.
Installation & Operation manual of Jetmaster Vent Free Drop In Fireplace STEP 7 INCORRECT PEBBLE PLACEMENT WILL RESULT IN UNACCEPTABLE AND POTENTIALLY DANGEROUS CONDITIONS. Place a row of pebbles directly above the burner opening between the front and back V-board panels. These pebbles must be spaced 10mm –...
Installation & Operation manual of Jetmaster Vent Free Drop In Fireplace The final phase of the installation is to verify the flame pattern, and to confirm that the unit functions correctly. Switch on the unit and monitor the flame pattern.
Installation & Operation manual of Jetmaster Vent Free Drop In Fireplace OPERATION INSTRUCTIONS GENERAL If a gas smell is detected either when the unit is OFF or ON, action must be taken immediately Whenever a gas smell is detected, follow the following steps: Switch the unit OFF.
Installation & Operation manual of Jetmaster Vent Free Drop In Fireplace SETTING BURNER SIZE Press and release (+- 1 s) the max flame button (c). The valve will open fully for maximum flame Press and release (+- 1 s) the min flame button (d). The valve will reduce to the minimum flame setting.
• carried out in accordance with the installation and Operating Instructions current at the time of purchase. When a valid claim arises under this warranty, Jetmaster will, at its sole option, either repair or replace the Burner or firebox Under no circumstances will Jetmaster be liable for any consequential loss or damage or injury arising out of, or in connection with the use or operation of the Burner or firebox, resulting from the failure to follow the Installation and Operating Instructions, or from a breach of the Warranty conditions.