Mitsubishi Electric PUHY-P72 Service Manual page 139

City multi
Hide thumbs Also See for PUHY-P72:
Table of Contents

Advertisement

[ VIII Test Run Mode ]
Operation
Ambient
Indoor
tempera-
Outdoor
ture
No. of connected
units
Indoor
No. of units in opera-
unit
tion
Operating
Model
conditions
Main pipe
Piping
Branch pipe
Total pipe length
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
SC (LEV1)
ing
LEV2
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Discharge (TH4)
Heat exchanger out-
let (TH3)
Accumulator inlet
Outdoor
Accumulator outlet
unit
Temp. of
SCC outlet (TH6)
each sec-
tion
Compressor inlet
Compressor shell
bottom
LEV inlet
Indoor
Heat exchanger
unit
outlet
HWE0804A
PUHY-P96THMU-A
26.7 °C /19.4 °C [80 °F/67 °F]
DB/WB
Unit
-
m [ft]
-
kg
[lbs-oz]
A
V
Hz
65
222/325/325/325/387/387
Pulse
159
1400
MPa
[psi]
2.88/0.87 [417/126]
74 [165]
46 [115]
10 [50]
10 [50]
26 [79]
°C [°F]
14 [57]
38 [100]
25 [77]
10 [50]
- 130 -
Outdoor unit model
PUHY-P216TSHMU-A
PUHY-P120THMU-A
35 °C / - [95 °F/ - ]
6
6
06/36/36/36/48/48
5 [16-3/8]
10 [32-3/4]
65 [213-1/4]
Hi
25 [55]
53.2
230
71
237
1400
2.88/0.87 [417/126]
73 [163]
40 [104]
10 [50]
10 [50]
20 [68]
15 [59]
42 [108]
19 [66]
10 [50]
GB