[ VIII Test Run Mode ]
Operation
Ambient
Indoor
tempera-
Outdoor
ture
No. of connected
units
Indoor
No. of units in opera-
unit
tion
Operating
Model
conditions
Main pipe
Piping
Branch pipe
Total pipe length
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
SC (LEV1)
ing
LEV2
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Discharge (TH4)
Heat exchanger out-
let (TH3)
Accumulator inlet
Outdoor
unit
Accumulator outlet
Temp. of
each sec-
Compressor inlet
tion
Compressor shell
bottom
LEV inlet
Indoor
Heat exchanger
unit
inlet
HWE0804A
PUHY-
P120THMU-A
DB/WB
Unit
-
m [ft]
-
kg
[lbs-oz]
A
V
Hz
78
332/332/332/406/406/406/406
Pulse
1280
2.70/0.65
MPa
[psi]
[392/94]
70 [158]
-1 [30]
-1 [30]
-1 [30]
°C [°F]
-1 [30]
40 [104]
36 [97]
69 [156]
- 146 -
Outdoor unit model
PUHY-P360TSHMU-A
PUHY-
P120THMU-A
P120THMU-A
21.1°C/ - [70°F/ - ]
8.3°C/6.1°C [47°F/43°F]
7
7
48/48/48/54/54/54/54
5 [16-3/8 ]
10 [32-3/4 ]
75 [246-1/16]
Hi
39 [86]
79.7
230
78
0
1280
2.70/0.65
[392/94]
70 [158]
-1 [30]
-1 [30]
-1 [30]
-1 [30]
40 [104]
36 [97]
69 [156]
PUHY-
78
1280
2.70/0.65
[392/94]
70 [158]
-1 [30]
-1 [30]
-1 [30]
-1 [30]
40 [104]
36 [97]
69 [156]