Installation Guide..................8 Moving the Unit..........................8 Plugging in the Unit.........................8 Operation.....................9 Control Panel...........................9 Maintenance....................10 Filter Cleaning..........................10 Spring Replacement........................11 Troubleshooting..................11 Alarm Codes...........................12 Troubleshooting Chart........................13 Specifications.....................14 Shipping List....................14 Options......................14 Obtaining Service..................15 Xtreme Power Conversion Limited Warranty..........16 Xtreme Power Conversion Corporation Page 2...
Page 3
Thank you for selecting this Xtreme Cooling unit. It provides you with spot cooling for large areas where cooling of an entire area is not practical or possible. Please read this manual before installing the XC-14A, XC-22A, or XC-30A as it provides important information that should be followed during installation and maintenance of the Portable Air Conditioner, allowing you to correctly set up your system for the maximum safety and performance.
Page 4
22. Only use the unit in the upright position on a even, flat surface. Unit must be positioned at least 24 inches (60 cm) from the nearest object in any direction. 23. Stop operation immediately if abnormal noise or odor is noticed. Contact local service center. Xtreme Power Conversion Corporation Page 4...
If an abnormal operation occurs, a visual display of the fault is shown. Caster wheels are included for ease of portability. Suitable applications include: factory or work place, industrial kitchen, computer room, emergency cooling, out- door event, etc. Xtreme Power Conversion Corporation Page 5...
XC User’s Manual Portable Air Conditioning Assembly Component Parts Front and Right Side View Rear and Left Side View Xtreme Power Conversion Corporation Page 6...
2. Place the Rubber Stoppers on the rear of the unit as shown below 3. Use screws to install the Rubber Stoppers to the rear of the unit (screws inside the accessory box) Rubber Stopper attachment Xtreme Power Conversion Corporation Page 7...
If any damage or excess play is found, contact a qualified repair technician or a qualified electrician to perform replacement of repair of the power cord, plug, or prongs. WARNING! If the power cord or plug are damaged, repair should only be performed by qualified electrical person- nel. Xtreme Power Conversion Corporation Page 8...
NOTE: Make sure the AC outlet is free of dirt, dust, oil, water, or any other foreign material. The unit is equipped with an approved NEMA plug configuration (XC-14A = 5-15P; XC-22A = 6-15P; XC-30A = 6-20P). The appropriate outlet must be used for each plug type.
Do not use any other chemicals to clean the filter, as they will likely damage the filter. 4. Dry the filter in a shaded area before replacing it. Do not operate the unit without the filter installed and the filter guard in the closed position. Xtreme Power Conversion Corporation Page 10...
3 minutes, the unit will resume operation. If the fault persists for more than 3 minutes, the evaporator fan also stops. The fault must be rectified before the unit can resume normal operation. Xtreme Power Conversion Corporation Page 11...
Replace compressor a. Empty the water tank b. After installation of the Condensate water level water tank, press the Condensate tank is full alarm SPOT / COOL or ROOM / COOL button to resume operation Xtreme Power Conversion Corporation Page 12...
No cause pressor shuts off after unit shuts off Alarm displays “FT” with less than Replace the spring (see Mainte- half of the condensate water in the Spring is possibly broken nance section) tank Xtreme Power Conversion Corporation Page 13...
RMA number marked on the outside of the boxes. 4. Return the UPS by insured, prepaid carrier to the address provided by the Technician. 5. Refer to the Warranty statements in this manual for additional details on what is covered. Xtreme Power Conversion Corporation Page 15...
Purchaser’s sole and exclusive remedy for breach of any warranty, expressed or implied, concerning Xtreme Power Conversion equipment, and the only obligation of XPC Corporation under this warranty, shall be the repair or replacement of defective equipment, components, or parts;...