free hit counter

Outdoor Unit (Ras-13N2A-Hx); Outdoor Unit (Ras-10N2A-Hx) - Toshiba RAS-13NKHP-E2 Service Manual

Air conditioner split wall type
Table of Contents

Advertisement

4-5. Outdoor Unit (RAS-13N2A-HX)

No.
P
ar
ts name
1
Compressor
2
Fan motor (for outdoor)
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
Overload relay
5

4-6. Outdoor Unit (RAS-10N2A-HX)

No.
P
ar
ts name
1
Compressor
2
Fan motor (for outdoor)
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
Overload relay
5
Type
Output (Rated) 1100 W, 2 poles, 1 phase, 220 - 240 V, 50Hz
RM5515FNE96
Winding resistance (W)
(at 20°C)
Output (Rated) 20 W, 6 poles, 1 phase, 220 - 240 V, 50Hz
HF-240-42A
Winding resistance (W)
(at 20°C)
DS451155NPQB AC 450 V, 1.5 F
RS44B256U0213S AC 440 V, 25 F
LPAP960B
U/T : 6.1A (80°C), OPEN : 135±5°C, CLOSE : 78±11°C
Type
Output (Rated) 750 W, 2 poles, 1 phase, 220 - 240 V, 50Hz
RM5510GNE94
Winding resistance (W)
(at 20°C)
Output (Rated) 20 W, 6 poles, 1 phase, 220 - 240 V, 50Hz
HF-240-30B
Winding resistance (W)
(at 20°C)
DS451155NPQB AC 450 V, 1.5 F
RS44B256U0213S AC 440 V, 25 F
LPAP960B
U/T : 6.1A (80°C), OPEN : 135±5°C, CLOSE : 78±11°C
- 16 -
FILE NO. SVM-06001
Specifications
C-R
2.43
Red-Black
176.2
m
m
Specifications
C-R
3.710
Red-Black
245
m
m
C-S
3.78
White-Black
290.5
C-S
4.099
White-Black
388