Error detected by TCC-LINK central control device
Check code
Display on
Outdoor 7-segment display
central control
Check code
Auxiliary code
device
C05
—
C06
—
C12
—
P30
Differs according to
error contents of the with alarm
(L20 is displayed.)
Detected position
Check code name
TCC-LINK
TCC-LINK central control device
transmission error
TCC-LINK central control device
transmission error
General-purpose equipment
General-purpose controller control
I/F
Interface batched alarm
TCC-LINK
Follower unit error of group control
Duplicated central control address
Status
Error detection condition
Operation
Signal is not transmit from
• Check central control device error.
continued.
central control device.
• Check communication line error of central control device.
• Check setup of terminator resistor.
Operation
Signal is not received from
• Check central control device error.
continued.
central control device.
• Check communication line error of central control device.
• Check setup of terminator resistor.
• Check the power of connecting destination connected device.
• Check P .C. board error of the connected device.
Operation
Error was input in general-
• Check error input.
continued.
purpose equipment control
interface.
Operation
An error occurred in follower
• Check the check code of the unit with alarm.
continued.
unit of the group control.
([P30] is displayed only on the
central remote controller.)
Operation
Central control addresses
• Check the address setup.
continued.
were duplicated.
Check item (position)