Chapter 6
Cisco ASR 1006 Router Overview and Installation
Each DC input power cable is terminated at the PDU by a cable lug. The cable lugs must be
dual-hole, and have a straight tongue. They must be able to fit over 1/4-inch terminal studs at
0.625-inch (15.88-mm) centers.
Note
A ground cable is required for each DC PDU. We recommend that you use at least 6-AWG
multistrand copper wire. This wire is not available from Cisco Systems; it is available from any
commercial cable vendor.
The ground wire cable lug should be dual-hole (see
studs at 0.625 inch (15.88mm) centers. Recommended lug terminal wire size Panduit part number:
Figure 6-20
End View
0.48
0.08
Note
When you install the unit, the ground connection must always be made first and disconnected last.
Warning
Statement 1046
To connect the DC power supply, follow these steps:
Make certain that the chassis grounding is connected before you begin installing the DC power supply.
Step 1
Locate the stud on the DC power supply for the GND connection which must be connected first and
Step 2
follow these steps:
Using the grounding lug, replace the washers and Kepnut screw in the following order.
a.
OL-13208-11
DC input power cables must be connected to the PDU terminal studs in the proper positive
(+) and negative (–) polarity. In some cases, the DC cable leads are labeled, which is a
relatively safe indication of the polarity. However, you must verify the polarity by measuring
the voltage between the DC cable leads. When making the measurement, the positive (+)
lead and the negative (–) lead must always match the (+) and (–) labels on the power
distribution unit.
LCD8-14A-L for 8AWG wire size
LCD6-14A-L for 6AWG wire size
DC Input Power Cable Lug
Ø 0.267
2 holes
0.25
0.63
To avoid hazardous conditions, all components in the area where DC input power is
accessible must be properly insulated. Therefore, before installing the DC cable lugs, be sure
to insulate the lugs according to the manufacturer's instructions.
Flat washer
Cisco ASR 1000 Series Aggregation Services Routers Hardware Installation Guide
Connecting Power to the Cisco ASR 1006 Router
Figure
All measurements in inches
2.24
Crimp area
0.37
6-20) and able to fit over M6 terminal
6-29