Set Temp. Correction - Toshiba RAS-10SAVP-E Service Manual

Hide thumbs Also See for RAS-10SAVP-E:
Table of Contents

Advertisement

Toshiba ilmalämpöpumppujen myynti, huolto ja asennus: Jäähdytinpalvelu RefGroup Oy, Vantaa
Item
Operation flow and applicable data, etc.
18. Set temp.
<Indoor control P.C. board (At shipment)>
correction
<In HEAT operation>
Jumper wire setup
J801
×
×
¡
¡
¡
: With Jumper wire
×
: Cut Jumper wire
<In 8°C HEAT operation> (–ND model only)
Jumper wire setup
J803
×
×
¡
¡
¡
: With Jumper wire
×
: Cut Jumper wire
Jumper wire
HEAT
shift value
J802
×
–2
¡
+4
×
+2
← At shipment
¡
0
HEAT
shift value
J804
×
–2
¡
+4
×
+2
← At shipment
¡
0
www.ilmalämpöpumput.com
– 45 –
1. Purpose
When the difference between the set
temp. of the remote controller and the
room temp. is wide due to the installation
condition, etc, the set temp. is corrected.
(HEAT operation only)
2. Description
The set temp. received from the remote
controller is corrected. The correct value
from –2°C to +4°C is changed by the
jumper wire on P.C. board of the indoor
microcomputer.
J801
J802
J803
J804
Description