free hit counter

Part Names And Functions; Specification - Mitsubishi Electric MUCF-GA35VB Service Manual

Floor and ceiling type air conditioners wireless type models
Table of Contents

Advertisement

2

PART NAMES AND FUNCTIONS

MUCF-GA35VB
3

SPECIFICATION

Outdoor model
Function
Power supply
Capacity
Dehumidification
Air flow(High)
Power outlet
Runnning current
Power input
Power factor
Starting current
Compressor motor current
Fan motor current
Coefficient of performance(C.O.P)
Model
Output
Winding
resistance(at 20:)
Model
Winding
resistance(at 20:)
Dimensions WOHOD
Weight
Sound level(High)
Fan speed(High)
Fan speed regulator
Refrigerant filling
capacity(R410A)
Refrigeration oil (Model)
NOTE: Test conditions are based on ISO 5151
Cooling : Indoor
Outdoor DB35°C WB(24°C)
Indoor-Outdoor piping length : 5m
Air inlet
(back and side)
Piping
Drain hose
Air outlet
Drain outlet
MUCF-GA35VB
Single phase
230V, 50Hz
kW
r/h
K /h
A
A
W
%
A
A
A
RN135VHSHT
W
C-R 2.79
"
C-S 3.36
RA6V33-JC
WHT-BLK 215
"
BLK-RED 307
mm
780o540o255
kg
dB
rpm
kg
cc
620 (NEO22)
DB27°C WB19°C
MUCF-GA50VB
MUCF-GA60VB
MUCF-GA50VB
Cooling
Single phase
3.5
1.5
1,914
10
4.89
1,104
98
29
4.58
0.31
3.02
RN196VHSHT
900
WHT-BLK 79.5
BLK-RED 83.0
850o605o290
36
49
825
1
0.75
520 (NEO22)
5
Cooling
230V, 50Hz
4.8
2.4
2,196
15
7.98
1,744
95
37
7.59
0.39
2.65
1,300
C-R 1.80
C-S 3.00
RA6V50-PA
44
52
825
1
1.45
Air inlet
(back and side)
Piping
Drain hose
Air outlet
Drain outlet
MUCF-GA60VB
Cooling
Single phase
230V, 50Hz
6.0
3.1
2,322
25
10.62
2,370
97
74
10.07
0.55
2.45
NN29VBAHT
1,900
C-R 0.80
C-S 1.64
RA6V60-MA
WHT-BLK 71
BLK-RED 89
850o605o290
60
53
873
1
1.85
1,200 (NEO22)

Hide quick links:

Advertisement

Table of Contents
loading