free hit counter

Configuring The Battery Charge Power Levels - HP R12000 User Manual

Directflow ups
Hide thumbs Also See for R12000:
Table of Contents

Advertisement

Main menu
Identification
* An asterisk indicates the factory default setting.

Configuring the battery charge power levels

Different battery charge power levels can be set in the power unit for utility and generator input sources. A
higher charge power level like 1100 W or 550 W can be set for utility input, and a lower charge level, 190
W or 0 W, can be set for generator input to reserve AC power for loads while running on generator input.
By default, the power unit uses a built-in algorithm to determine when to switch battery charge power levels.
For instance, when there is a power outage the UPS transfers from AC mode to Battery mode. If the input AC
becomes available before 10 seconds or after 60 seconds, the power unit automatically remains at the
charge power level defined for utility input. However, if the input AC becomes available again between 10
and 60 seconds, the power unit switches to the battery charge power level defined for generator input. The
power unit remains at the generator charge power level until the defined on-generator time period expires,
and then the power unit switches back to the charge power level defined for utility input.
To set the power unit battery charge power levels from the Settings menu:
Select Input source, scroll to Utility & Gen, and then press Enter.
1.
Utility & Gen is the default setting. To disable the built-in algorithm, select Utility Only.
Submenu
Display information or
menu option
50Hz
Input Source
Util Only
Util & Gen*
On-Gen Duration
30 min*
1 hr
2 hr
4 hr
Run Time Limitation
Yes
No*
PU P/N:
PU S/N:
PU SYS FW:
PU PWR FW:
BP1 P/N:
BP1 S/N:
BP1 FW:
BP2 P/N:
BP2 S/N:
BP2 FW:
Description
AC input from utility power
source only
AC input from utility and
generator power sources
Time period that unit uses
generator power settings
Enable the maximum battery
run time limitation
Power unit model
Power unit serial number
Power unit system firmware
version
Power unit power firmware
version
Battery pack 1 model (closest
to power unit)
Battery pack 1 serial number
Battery pack 1 firmware
version
Battery pack 2 model
Battery pack 2 serial number
Battery pack 2 firmware
version
UPS operations 75

Hide quick links:

Advertisement

Table of Contents
loading