Check of outdoor unit
Compressor and outdoor fan do not operate.(Only indoor fan operates.)
Start
Press EMERGENCY ON/OFF button.
3-minute time delay works.
Test mode operates for 30 minutes.
Check voltage to terminal block of outdoor unit. Is
there 115V AC to terminal block between
-
?
L2
N
Check voltage to terminal block of outdoor unit. Is
there DC12V to terminal block between 2 2 - 1 1 ?
Check the outdoor fan motor , compressor , relay ,
contactor , and wiring.
No
-
,
L1
N
Yes
No
Yes
Yes
Check voltage to terminal block of indoor unit. Is
there DC12V to terminal block between 2 2 - 1 1 ?
Check the indoor, outdoor connection.
Turn on outdoor power supply.
Check the indooor electronic control
P.C.board and wiring.
No
13