free hit counter

Digital Input - Honeywell NFS Supra Installation And Operating Manual

Conventional fire alarm control panel
Table of Contents

Advertisement

NFS Supra

5.4.5 Digital Input

The digital input of the control panel activates by close contact (by default) or open contact
(Configurable option). When the contact is closed/opened between digital input terminals
(DIGITAL IN), the following functions are supported by the control panel:
Digital input configuration:
Select by pressing KEYPAD ACCESS=ON
The cyclic change of the function is made by pressing the RESET key.
Led 1 Alarm (Red)
= ON
Led 2 Disablement (Yellow)
= ON
Led 3 Test (Yellow)
= ON
Led 4 Power (Green)
= ON
Led 5 General Fault (Yellow)
= ON
Digital input activates by close contact (by default) (when closes activates)
Digital input activation selection NO/NC:
Select by pressing keys (KEYPAD ACCESS=ON + SILENCE/RESOUND =ON)
The cyclic change of the function is made by pressing the RESET key.
Led 1 Alarm (Red)
= ON; activates by NC contact
Led 2 Disablement (Yellow)
= ON; Activates by NO contact (By default)
HLS-MN-025 v.04
www.honeywelllifesafety.es
www.hoeywelllifesafety.es
Reset (By default)
Evacuate
Sounders and Buzzer mute
Delays on/off
Buzzer Mute
Digital input
function
change
Reset push-button: Change Option (Access level 3 - Configuration)
Change
option
Reset push-button: Change Option (Access level 3 - Configuration)
Configuration
Installation and Operating Manual
Page 41

Hide quick links:

Advertisement

Table of Contents
loading