FEATURES 1-1. INDOOR UNIT 1-1-1. COMPACT CASSETTE TYPE MODELS : AUU7RLF, AUU9RLF, AUU12RLF, AUU18RLF „ „ FEATURES „ „ Quiet quality „ 2-stage turbo fan „ Optimization of wing form (laminar High efficiency design by 2 stage structure wing type) and wing number (7 blades...
1-1-2. SLIM DUCT TYPE MODELS : ARU7RLF, ARU9RLF, ARU12RLF, ARU18RLF, ARU24RLF „ „ Slim design and wide range of static pressure for flexible installation. FEATURES „ „ Slim design Air - intake „ „ This model is slim design, it can install at Air intake direction can be selected to the place where a ceiling is narrow.
MODELS : ASU7RLF, ASU9RLF, ASU12RLF „ „ Compact and Stylish design indoor unit FEATURES „ „ High density heat transfer tube „ arrangement Easy maintenance „ Removable & Making the tube Ø5 washable Thin: 0.276inch (7mm) ▼ panel 0.197inch (5mm) Volume reduction of heat exchanger: Dry operation...
Page 9
MODELS : ASU9RLS2, ASU12RLS2, ASU15RLS2 „ „ FEATURES „ „ Thin & Slim design „ Thin and slim design is realized by Ø5mm heat Big open panel and High density multi path heat exchanger and high efficiency wind blower. exchanger Large intake Refrigerant Ø3/16in.
1-1-4. FLOOR TYPE MODELS : AGU9RLF, AGU12RLF, AGU15RLF „ „ FEATURES „ „ 2-Fan & Wide airflow „ Heating Prevents cold Window Cooling Prevents cold air draft from from falling window at operation at operation at stable at stable start start operation operation...
1-2. LINE UP MODEL „ „ INDOOR UNIT AUU7RLF ARU7RLF ARU18RLF AUU9RLF ARU9RLF AUU12RLF ARU12RLF AUU18RLF ARU24RLF ASU7RLF1 ASU7RLF ASU9RLF1 ASU9RLF ASU12RLF1 ASU12RLF ASU9RLS2 ASU18RLF AGU9RLF ASU12RLS2 ASU24RLF AGU12RLF ASU15RLS2 AGU15RLF OUTDOOR UNIT AOU18RLXFZ AOU24RLXFZ AOU36RLXFZ1 Indoor units that can be connected to each outdoor unit „...
REMOTE CONTROLLER 2-1. WIRELESS REMOTE CONTROLLER MODEL: UTY-LNHUM/AR-RAH1U „ „ FEATURES „ „ ● 4 mode timer setup available (ON / OFF / PROGRAM /SLEEP). ● Can be used jointly with wired remote controllers . ● Easy to change custom code (max. 4 custom codes) by button operation. Built-in timers „...
SYSTEM DIAGRAM „ „ ● Control signal might not be recognized in following cases: (i) A curtain or a wall, etc. exists between transmitter and receiver. (ii) There is an instant-start type (inverter type, etc.) fluorescent lamp Signal receiver Signal transmitter in the room.
PACKING LIST „ „ Name and shape Quantity Application Use as remote controller holder Remote controller holder For remote controller holder installation Tapping screw Battery For remote controller [ 1.5V (R03 / AAA) ] SPECIFICATIONS „ „ Dimensions [H x W x D]: in. (mm) 6-11/16 (170) x 2-3/16 (56) x 3/4 (19) Weight : oz.
MODEL: AR-RED1U „ „ FEATURES „ „ 5 Mode timer setup Ü „ (ON / OFF / Weekly / Program / Sleep) are possible. Easy operation. Ü „ Easy to change custom code (max. 4 custom codes) by button Ü „...
Page 21
FUNCTIONS (AR-RED1U) „ „ SENSOR button Signal Transmitter MODE button FAN button MIN. HEAT button ECONOMY button SWING button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button START/STOP ON/OFF button button SEND button SLEEP button SELECT button RESET button...
Page 22
SYSTEM DIAGRAM „ „ ● Control signal might not be recognized in following cases: (i) A curtain or a wall, etc. exists between transmitter and receiver. (ii) There is an instant-start type (inverter type, etc.) fluorescent lamp Signal transmitter Signal receiver in the room.
Page 23
PACKING LIST „ „ Name and shape Quantity Application Use as remote controller holder Remote controller holder For remote controller holder installation Tapping screw Battery For remote controller [ 1.5V (LR03 / AAA) ] SPECIFICATIONS „ „ Dimensions [H x W x D]: in.(mm) 8-1/16 (205) ×...
Page 24
MODEL: AR-REG1U „ „ FEATURES „ „ Ü 4 mode timer setup available (ON / OFF / PROGRAM / SLEEP). Ü Easy operation. Ü Easy to change custom code (max. 4 custom codes) by button operation. REG1U Built-in timers „ Select from four different timer programs (On / Off / Program / Sleep).
Page 25
FUNCTIONS (AR-REG1U) „ „ Signal transmitter MODE button FAN button MIN. HEAT button ECONOMY button SWING button TEMP. button SET button POWERFUL button TIMER ON button Start/Stop button TIMER OFF button TIMER SELECT button RESET button °C / °F switching button TIMER SLEEP button CLOCK ADJUST button TIMER CANCEL button...
Page 26
SYSTEM DIAGRAM „ „ ● Control signal might not be recognized in following cases: (i) A curtain or a wall, etc. exists between transmitter and receiver. (ii) There is an instant-start type (inverter type, etc.) fluorescent lamp Signal receiver window Signal transmitter in the room.
Page 27
PACKING LIST „ „ Name and shape Quantity Application Use as remote controller holder Remote controller holder For remote controller holder installation Tapping screw Battery For remote controller [ 1.5V (LR03 / AAA) ] SPECIFICATIONS „ „ Dimensions [H x W x D]: in.(mm) 8-1/16 (205) ×...
2-2. WIRED REMOTE CONTROLLER (For Compact cassette type, Slim duct type) FEATURES ● Various timer setup (ON/OFF/WEEKLY) are possible. „ „ ● Equipped with weekly timer as standard function. (Start/Stop function is twice per day for a week) ● When setting up a timer, start/stop and a temperature setup can be changed.
Page 29
FUNCTIONS „ „ START/STOP button Pressed to start and stop operation. SET TEMP. button Display Selects the setting temperature. MODE button Selects the operating mode ( AUTO , COOL , DRY , , HEAT FAN button , MED Selects the fan speed ( AUTO , HIGH , QUIET Vertical air flow direction and swing button...
SYSTEM DIAGRAM „ „ 1 remote controller z 2 remote controllers „ Indoor unit Indoor unit A , B , C : Remote controller cable. < < 1,640ft (500m) ; B+C 1,640ft (500m) Secon- Primary dary Remote controller Remote controllers ELECTRICAL WIRING „...
Page 31
INSTALLATION „ „ Connection Pattern „ Note: Connection pattern is different according to type of Indoor unit. Indoor unit types Connection Pattern Compact Cassette type Pattern A Slim Duct type ASU7RLF1, ASU9RLF1, ASU12RLF1 ASU7RLF, ASU9RLF, ASU12RLF Pattern B Wall Mounted type ASU9RLS2, ASU12RLS2, ASU15RLS2 ASU18RLF, ASU24RLF Pattern C...
Page 32
Pattern C „ 1) Modify the remote controller cable as per below methods. ● Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in Fig. ●...
PACKING LIST „ „ Name and shape Quantity Application Remote controller cable For connecting the remote controller [33ft(10m)] For installing the remote controller Screw (M4 x 16mm) For remote controller and remote controller cable Binder binding For connecting the remote controller cable to the Connecting cable Wall mounted type indoor unit For installing the remote controller cable to the...
SPECIFICATIONS 3-1. COMPACT CASSETTE TYPE Model name AUU7RLF AUU9RLF AUU12RLF AUU18RLF Power source 1ø 208/230V 60Hz Available voltage range 187-264V Capacity 7,000 Btu/h class 9,000 Btu/h class 12,000 Btu/h class 18,000 Btu/h class Input power Running current 0.15 0.15 0.19 0.30...
3-2. SLIM DUCT TYPE Model name ARU7RLF ARU9RLF ARU12RLF ARU18RLF ARU24RLF Power source 1ø 208/230V 60Hz Available voltage range 187-264V 7,000 Btu/h 9,000 Btu/h 12,000 Btu/h 18,000 Btu/h 24,000 Btu/h Capacity class class class class class Input power Running current 0.30 0.30 0.35...
3-3. WALL MOUNTED TYPE Model name ASU7RLF1 ASU9RLF1 ASU12RLF1 Power source 1ø 208/230V 60Hz Available voltage range 187-264V Capacity 7,000 Btu/h class 9,000 Btu/h class 12,000 Btu/h class Input power Running current 0.13 0.15 0.19 High 330 (560) 353 (600) 388 (660) 294 (500) 306 (520)
Page 37
Model name ASU7RLF ASU9RLF ASU12RLF Power source 1ø 208/230V 60Hz Available voltage range 187-264V Capacity 7,000 Btu/h class 9,000 Btu/h class 12,000 Btu/h class Input power Running current 0.13 0.15 0.19 High 330 (560) 353 (600) 388 (660) 294 (500) 306 (520) 330 (560) Cooling...
Page 38
Model name ASU9RLS2 ASU12RLS2 ASU15RLS2 Power source 208/230V~ 60Hz Available voltage range 187-264V Capacity 9,000 Btu/h class 12,000 Btu/h class 14,000 Btu/h class Input power Running current 0.14 0.17 0.20 High 353 (600) 388 (660) 418 (710) 324 (550) 353 (600) 377 (640) Cooling 277 (470)
Page 39
Model name ASU18RLF ASU24RLF Power source 1ø 208/230V 60Hz Available voltage range 187-264V Capacity 18,000 Btu/h class 24,000 Btu/h class Input power Running current 0.32 0.53 High 542 (920) 659 (1,120) 436 (740) 530 (900) Cooling 365 (620) 436 (740) Quiet 324 (550) 365 (620)
3-4. FLOOR TYPE Model name AGU9RLF AGU12RLF AGU15RLF Power source 1ø 208/230V 60Hz Available voltage range 187-264V Capacity 9,000 Btu/h class 12,000 Btu/h class 14,000 Btu/h class Input power Running current 0.15 0.18 0.20 High 312 (530) 353 (600) 383 (650) 259 (440) 288 (490) 306 (520)
DIMENSIONS 4-1. COMPACT CASSETTE TYPE MODELS : AUU7RLF, AUU9RLF, AUU12RLF, AUU18RLF „ „ Unit: in. (mm) • Cassette grille mounting state 20-7/8 (530): Hanging bolt position 5-5/16 9-13/16 (250) (135) op view Be sure to leave Maintenance space maintenance space...
INSTALLATION PLACE „ „ Unit : in. (mm) Strong and durable ceiling 11 (262) or more 40 (1,000) 40 (1,000) or more or more 95 (2,400) or more Obstruction Floor H (The maximum height from floor to ceiling) Unit: in. (mm) Model name AUU7 AUU9...
4-2. SLIM DUCT TYPE Unit : in. (mm) MODELS : ARU7RLF, ARU9RLF, ARU12RLF „ „ 2 (51) 22-5/8 (574) View A Rear view (Drain hose) Drain port 3-15/16 (100) x 6 = 23-5/8 (600) 1-7/8 (47) 25-9/16 (650) 2-3/16 (55) 3-1/16 (78) 28-7/8 (734) 3-1/2 (89)
Page 44
MODEL : ARU18RLF „ „ Unit : in. (mm) 2 (51) 30-1/2 (774) Rear view View A (Drain hose) Drain port 1-7/8 (47) 3-15/16 (100) x 8 = 31-1/2 (800) 2-3/16 (55) 3-1/16 (78) 33-7/16 (850) 3-1/2 (89) 36-3/4 (934) 4-11/16 (119) Top view 3-7/16 (87)
Page 45
MODEL : ARU24RLF „ „ Unit : in. (mm) 38-3/8 (974) 2 (51) View A Rear view (Drain hose) Drain port 3-15/16 (100) x 10 = 39-3/8 (1,000) 1-7/8 (47) 2-3/16 (55) 3-1/16 (78) 41-5/16 (1,050) 44-5/8 (1,134) 3-1/2 (89) 3-7/16 (87) 4-11/16 (119) Top view...
Page 46
Unit : in. (mm) INSTALLATION PLACE „ „ 12 (300) or more Strong and durable ceiling 1 (20) or more Indoor unit Left Right side side 1 (20) or more 12 (300) 4 (100) Service access Ceiling or more or more Floor 1 (10) 1 (10)
Page 47
Unit : in. (mm) MAINTENANCE SPACE „ „ Provide a service access for inspection purposes as shown below. Do not place any wiring or illumination in the service space, as they will impede service. Service access Unit Control 12 (300) or more Service space - (01 - 43) -...
4-3. WALL MOUNTED TYPE MODELS : AS U7RLF1, ASU9RLF1, ASU12RLF1 „ „ Unit : in. (mm) 33-1/16 (840) 8 (203) (33-1/16(840)) 3-1/16(78) 1-3/4(45) 14-5/16(364) 13-7/8(353) Ø2-9/16 (Ø65) Ø2-9/16 (Ø65) for pipe inlet for pipe inlet 3-7/16 4-9/16 12-3/8(315) 12-5/8(321) (88) (116) ASU7RLF1, ASU9RLF1, ASU12RLF1 Liquid...
Page 49
INSTALLATION PLACE „ „ Unit : in. (mm) Outline of unit 1 (25) or more 3 (52) or more 3 (70) 6 (130) or more 60 (1,500) or more or more - (01 - 45) -...
Page 50
MODELS : AS U7RLF, ASU9RLF, ASU12RLF „ „ Unit : in. (mm) 8-1/16 (205) : Installed state 31-1/8 (790) 8 (203) 5-1/2 (140) *1 5-11/16 (145) *1 *1: Vertical flap is downward Outline of unit 3-11/16 (94) 17-11/16 (450) 11/16 (18) 2-1/16 (52) 8-1/4 (209) 9-5/16 (237)
Page 51
INSTALLATION PLACE „ „ Unit : in. (mm) Outline of unit 2 (48) or more 3 (52) or more 4 (100) or more 3 (70) or more 60 (1,500) or more - (01 - 47) -...
Page 52
MODELS : ASU9RLS2, ASU12RLS2, ASU15RLS2 „ „ Unit : in. (mm) 34-1/4 (870) 7-5/16 (185) 7-3/8(187) : Installed state Outline of Unit (34-1/4 (870)) 12-3/8 (315) 12-1/4 (311) Ø2-9/16 (65) Ø2-9/16 (65) for pipe inlet for pipe inlet 8-7/16 (214) 7 (178) (3-5/16 (84)) 13-7/8 (353)
Page 53
INSTALLATION PLACE „ „ Unit : in. (mm) Outline of Unit 2 (50) or more 2 (50) or more 7 (162) or more 7 (162) or more 60 (1,500) or more 10 (247) - (01 - 49) -...
Page 54
MODELS : ASU18RLF, ASU24RLF „ „ Unit : in. (mm) 39-5/16 (998) 20-1/2 (520) 23-1/4 (590) 9 (228) 1 (25) 28-3/8 (721) 20-1/2 (520) Unit center Outline of unit 1-1/8 (28) 2-5/8 (67) 35-9/16 (903) 13/16 (20) 15-5/8 (397) 17-1/4 (438) Ø...
Page 55
INSTALLATION PLACE „ „ Unit : in. (mm) Outline of unit 3 (52) or more 3 (53) or more 4 (80) or more 5 (120) or more 60 (1,500) or more - (01 - 51) -...
4-4. FLOOR TYPE MODELS : AG U9RLF, AGU12RLF, AGU15RLF „ „ Unit : in. (mm) 7-7/8 (200) 29-1/8 (740) Side view Front view INSTALLATION PLACE „ „ 4 (100) or more 4 (80) or more 4 (80) or more 2 (50) or more 4 (100) or below from the floor...
AIR VELOCITY AND TEMPERATURE DISTRIBUTIONS 6-1. COMPACT CASSETTE TYPE Conditions Fan speed : High MODEL : AUU7RLF, AUU9RLF Operation mode : FAN „ „ Air velocity distribution „ Top view Vertical airflow direction louver : Up (ft.) Unit : ft./s (m/s) 1 (0.25)
Note: Reference data Conditions Fan speed : High Operation mode : Heating Air velocity distribution „ Vertical airflow direction louver: Downward (4Way) Side view Vertical airflow direction louver : Down (ft.) Unit : ft./s (m/s) 7 (2.0) 7 (2.0) 5 (1.5) 5 (1.5) 3 (1.0) 3 (1.0)
Page 66
Conditions Fan speed : High MODEL : AUU12RLF Operation mode : FAN „ „ Air velocity distribution „ Top view Vertical airflow direction louver : Up (ft.) Unit : ft./s (m/s) 1 (0.25) 2 (0.5) 3 (1.0) 7 (2.0) 7 (2.0) 3 (1.0) 1 (0.25) 2 (0.5)
Page 67
Note: Reference data Conditions Fan speed : High Operation mode : Heating Vertical airflow direction louver: Air velocity distribution „ Downward (4Way) Side view Vertical airflow direction louver : Down (ft.) Unit : ft./s (m/s) 5 (1.5) 5 (1.5) 3 (1.0) 3 (1.0) 2 (0.5) 2 (0.5)
Page 68
Conditions Fan speed : High MODEL : AUU18RLF Operation mode : FAN „ „ Air velocity distribution „ Top view Vertical airflow direction louver : Up (ft.) Unit : ft./s (m/s) 1 (0.25) 2 (0.5) 3 (1.0) 7 (2.0) 7 (2.0) 1 (0.25) 2 (0.5) 3 (1.0)
Page 69
Note: Reference data Conditions Fan speed : High Operation mode : Heating Air velocity distribution „ Vertical airflow direction louver: Downward (4Way) Side view Vertical airflow direction louver : Down (ft.) Unit : ft./s (m/s) 7 (2.0) 7 (2.0) 5 (1.5) 5 (1.5) 3 (1.0) 3 (1.0)
6-2. SLIM DUCT TYPE with Auto louver grille kit MODEL : ARU7RLF „ „ Conditions Fan speed : High Note: This data is measured installing the Auto louver grille kit (option). Operation mode : Fan Air velocity distribution Voltage : 230V „...
Page 71
Reference Data Conditions Note: This data is measured installing the Auto louver grille kit (option). Fan speed : High Operation mode : Heating Air velocity distribution „ Voltage : 230V (ft.) Unit : ft./s (m/s) Side view 7 (2) 3 (1) Vertical airflow 2 (0.5) direction louver : Down...
Page 72
Conditions Fan speed : High MODEL : ARU9RLF „ „ Operation mode : Fan Voltage : 230V Note: This data is measured installing the Auto louver grille kit (option). Air velocity distribution „ (ft.) Unit : ft./s (m/s) Top view Vertical airflow 7 (2) direction louver : Up...
Page 73
Reference Data Conditions Note: This data is measured installing the Auto louver grille kit (option). Fan speed : High Operation mode : Heating Air velocity distribution „ Voltage : 230V (ft.) Unit : ft./s (m/s) Side view 7 (2) 3 (1) Vertical airflow 2 (0.5) direction louver : Down...
Page 74
Conditions Fan speed : High MODELS : ARU12RLF „ „ Operation mode : Fan Voltage : 230V Note: This data is measured installing the Auto louver grille kit (option). Air velocity distribution „ (ft.) Unit : ft./s (m/s) Top view Vertical airflow 7 (2) direction louver : Up...
Page 75
Reference Data Conditions Note: This data is measured installing the Auto louver grille kit (option). Fan speed : High Operation mode : Heating Air velocity distribution „ Voltage : 230V (ft.) Unit : ft./s (m/s) Side view 7 (2) 3 (1) Vertical airflow direction louver : Down 2 (0.5)
Page 76
Conditions Fan speed : High MODELS : ARU18RLF „ „ Operation mode : Fan Voltage : 230V Note: This data is measured installing the Auto louver grille kit (option). Air velocity distribution „ (ft.) Unit : ft./s (m/s) Top view Vertical airflow 7 (2) direction louver : Up...
Page 77
Reference Data Conditions Note: This data is measured installing the Auto louver grille kit (option). Fan speed : High Operation mode : Heating Air velocity distribution „ Voltage : 230V (ft.) Unit : ft./s (m/s) Side view 7 (2) Vertical airflow direction louver : Down 3 (1) 2 (0.5)
Page 78
Conditions MODEL : ARU24RLF Fan speed : High „ „ Operation mode : Fan Note: This data is measured installing the Auto louver grille kit (option). Voltage : 230V Air velocity distribution „ (ft.) Unit : ft./s (m/s) Top view Vertical airflow 7 (2) direction louver : Up...
Page 79
Conditions Fan speed : High Note: This data is measured installing the Auto louver grille kit (option). Operation mode : Heat Air velocity distribution Voltage : 230V „ Reference Data (ft.) Unit : ft./s (m/s) Side view 7 (2) Vertical airflow direction louver : Down 3 (1) 2 (0.5)
6-3. WALL MOUNTED TYPE Conditions Fan speed : High MODEL : AS U7RLF1 „ „ Operation mode : Fan (ft.) Unit : ft./s (m/s) Top view 7 (2.0) Vertical airflow direction louver : Up 3 (1.0) 2 (0.5) Horizontal airflow direction louver : Center (ft.)
Page 81
Conditions Fan speed : High MODEL : AS U9RLF1 „ „ Operation mode : Fan (ft.) Unit : ft./s (m/s) Top view 7 (2.0) Vertical airflow direction louver : Up 3 (1.0) 2 (0.5) Horizontal airflow direction louver : Center (ft.) (ft.) 3 (1.0)
Page 82
Conditions Fan speed : High MODEL : AS U12RLF1 „ „ Operation mode : Fan (ft.) Unit : ft./s (m/s) 7 (2.0) Top view Vertical airflow direction louver : Up 3 (1.0) 2 (0.5) Horizontal airflow direction louver : Center (ft.) (ft.) 3 (1.0)
Page 83
Conditions MODEL : AS U7RLF Fan speed : High „ „ Operation mode : Fan Unit : ft./s (m/s) (ft.) Top view Vertical airflow direction louver : Up 7 (2.0) 3 (1.0) 2 (0.5) Horizontal airflow direction louver : Center (ft.) (ft.) Top view...
Page 84
Conditions MODEL : AS U9RLF Fan speed : High „ „ Operation mode : Fan Unit : ft./s (m/s) (ft.) Top view Vertical airflow direction louver : Up 3 (1.0) 7 (2.0) 2 (0.5) Horizontal airflow direction louver : Center (ft.) (ft.) Top view...
Page 85
Conditions MODEL : AS U12RLF Fan speed : High „ „ Operation mode : Fan Unit : ft./s (m/s) (ft.) Top view Vertical airflow direction louver : Up 3 (1.0) 7 (2.0) 2 (0.5) Horizontal airflow direction louver : Center (ft.) (ft.) Top view...
Page 86
Conditions MODEL : AS U9RLS2 Fan speed : High „ „ Operation mode : Fan Unit : ft./s (m/s) (ft.) Top view Vertical airflow direction louver : Up 3 (1) 2 (0.5) 1 (0.25) Horizontal airflow direction louver : Center (ft.) (ft.) Top view...
Page 87
Conditions MODEL : ASU12RLS2, ASU15RLS2 Fan speed : High „ „ Operation mode : Fan Unit : ft./s (m/s) (ft.) Top view Vertical airflow direction louver : Up 3 (1) 2 (0.5) 1 (0.25) Horizontal airflow direction louver : Center (ft.) (ft.) Top view...
Page 88
Conditions MODEL : ASU18RLF Fan speed : High „ „ Operation mode : Fan (ft.) Unit : ft./s (m/s) Top view Vertical airflow 7 (2.0) 3 (1.0) 2 (0.5) direction louver : Up Horizontal airflow direction louver : Center (ft.) (ft.) Unit : ft./s (m/s) 2 (0.5)
Page 89
Conditions MODEL : ASU24RLF Fan speed : High „ „ Operation mode : Fan (ft.) Unit : ft./s (m/s) Top view Vertical airflow 2 (0.5) 7 (2.0) 3 (1.0) direction louver : Up Horizontal airflow direction louver : Center (ft.) (ft.) Unit : ft./s (m/s) 2 (0.5)
6-4. FLOOR TYPE MODELS : AGU9RLF, AGU12RLF, AGU15RLF „ „ Conditions Fan speed : High Unit : ft./s (m/s) (ft.) Operation mode : Fan Fan select : UPPER & LOWER 3(1.0) 2(0.5) Top view Vertical airflow direction louver : Up Horizontal airflow direction louver : Center UPPER...
AIRFLOW Air flow Air flow Operation Operation Type Model Type Model mode speed mode speed High High Cooling Cooling Quiet Quiet AUU7RLF ARU7RLF High High Heating Heating Quiet Quiet High High Cooling Cooling Quiet Quiet AUU9RLF ARU9RLF High High Heating...
Page 102
Air flow Air flow Operation Operation Type Model Type Model mode speed mode speed High High Cooling Cooling Quiet Quiet ASU7RLF1 ASU12RLS2 High High Heating Heating Quiet Quiet High High Cooling Cooling Quiet Quiet ASU9RLF1 ASU15RLS2 High High Heating Heating Quiet Quiet Wall...
NOISE LEVEL CURVE 9-1. COMPACT CASSETTE TYPE MODEL : AUU7RLF „ „ Cooling z Heating „ NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 HIGH NC-40 HIGH NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20...
Page 104
MODEL : AUU12RLF „ „ Cooling z Heating „ N C -65 N C -65 N C -60 N C -60 N C -55 N C -55 N C -50 N C -50 H igh N C -45 N C -45 H igh N C -40 N C -40...
9-2. SLIM DUCT TYPE MODEL : ARU7RLF „ „ Cooling z Heating „ NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000...
Page 106
MODEL : ARU12RLF „ „ Cooling z Heating „ N C -65 N C -65 N C -60 N C -60 N C -55 N C -55 N C -50 N C -50 N C -45 N C -45 N C -40 N C -40 N C -35 N C -35...
Page 107
MODEL : ARU24RLF „ „ Cooling z Heating „ N C -65 N C -65 N C -60 N C -60 N C -55 N C -55 N C -50 N C -50 N C -45 N C -45 N C -40 N C -40 H igh H igh...
9-3. WALL MOUNTED TYPE MODEL : AS U7RLF1 „ „ Cooling Heating „ „ N C -6 5 N C -6 5 N C -6 0 N C -6 0 N C -5 5 N C -5 5 N C -5 0 N C -5 0 N C -4 5 N C -4 5...
Page 109
MODEL : AS U12RLF1 „ „ Cooling Heating „ „ N C -6 5 N C -6 5 N C -6 0 N C -6 0 N C -5 5 N C -5 5 N C -5 0 N C -5 0 HIGH N C -4 5 N C -4 5...
Page 110
MODEL : AS U7RLF „ „ Cooling z Heating „ N C -65 N C -65 N C -60 N C -60 N C -55 N C -55 N C -50 N C -50 N C -45 N C -45 H igh H igh N C -40...
Page 111
MODEL : AS U12RLF „ „ Cooling z Heating „ N C -65 N C -65 N C -60 N C -60 N C -55 N C -55 N C -50 N C -50 H igh N C -45 N C -45 H igh N C -40 N C -40...
Page 112
MODEL : AS U9RLS2 „ „ Cooling z Heating „ N C -65 N C -65 N C -60 N C -60 N C -55 N C -55 N C -50 N C -50 N C -45 N C -45 N C -40 N C -40 H igh...
Page 113
MODEL : AS U15RLS2 „ „ Cooling z Heating „ N C -65 N C -65 N C -60 N C -60 N C -55 N C -55 N C -50 N C -50 N C -45 N C -45 H igh H igh N C -40...
Page 114
MODEL : AS U18RLF „ „ Cooling z Heating „ N C -65 N C -65 N C -60 N C -60 N C -55 N C -55 H igh N C -50 N C -50 H igh N C -45 N C -45 N C -40 N C -40...
EXTERNAL INPUT & OUTPUT EXTERNAL INPUT EXTERNAL OUTPUT Indoor unit type Operation status Fresh air control Auxiliary heater Control input Error status output output output output ● ● ● ― ― Compact Cassette ● ● ● ● ― Slim Duct ●...
Page 123
● When function setting is "Operation/Stop" mode Input signal Operation Indoor unit Stop ● When function setting is "Forced stop" mode Input signal Forced stop Command Normal Operation Indoor unit Stop Remote controller Remote control operation invalidity Parts (Optional) „ Wall Mounted Floor Compact...
12-2. EXTERNAL OUTPUT OPERATION STATUS OUTPUT „ „ Wall Mounted Floor Compact ASU7RLF ASU9RLS2 ASU7RLF1 AGU9RLF Slim Duct ASU18RLF ASU9RLF ASU12RLS2 ASU9RLF1 AGU12RLF Cassette ASU24RLF ASU12RLF ASU15RLS2 ASU12RLF1 AGU15RLF Connector CN103 CN103 CN304 CNB01 CN16 CN20 An air conditioner operation status signal can be output. Circuit diagram example „...
Page 125
FRESH AIR CONTROL OUTPUT „ „ Compact Cassette Slim Duct Wall Mounted Floor Connector ― ― A signal linked to air conditioner indoor fan ON can be output. * However, signal becomes OFF during cold air prevention control operation. Circuit diagram example „...
Page 126
AUXILIARY HEATER OUTPUT „ „ Compact Cassette Slim Duct Wall Mounted Floor Connector CN10 ― ― A signal is outputed from Connector when indoor fan and compressor turn on under heating operation. Tr-Ts * Signal output performance specifications are as Tr-Ts = -2°F( -1°C) shown on the right Tr-Ts = -6°F( -3°C)
Page 127
ERROR STATUS OUTPUT „ „ Wall Mounted Floor Compact ASU7RLF ASU9RLS2 ASU7RLF1 AGU9RLF Slim Duct ASU18RLF Cassette ASU9RLF ASU12RLS2 ASU9RLF1 AGU12RLF ASU24RLF ASU12RLF ASU15RLS2 ASU12RLF1 AGU15RLF Connector ― ― ― CNB02 ― CN21 An air conditioner error status signal can be output. Circuit diagram example „...
FUNCTION SETTINGS 13-1. INDOOR UNIT (setting by jumper wire) Note: This function is Slim Duct type only. SWITCH POSITION „ „ Slim Duct type „ JUMPER WIRE SETTING „ „ Drainage function setting (JM1) „ (u...Factory setting) Drainage function Connect Valid Disconnect Invalid...
13-2. INDOOR UNIT (setting by wireless remote controller) The function settings of the control of the indoor unit can be changed by this procedure ● „ according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. After the power is turned on, perform the “FUNCTION SETTING” according to the ●...
13-2-1. UTY-LNHUM/AR-RAH1U SWITCHING SELECTION OF FUNCTION SETTING MODE „ „ (2) Press and hold the “FAN” and the “ SET TEMP. ” buttons. While holding these 2 buttons, press the "RESET" button. SET TEMP. ( ) RESET Function setting mode display SELECTION AND CONFIRMATION OF CUSTOM CODE „...
Page 131
BUTTON NAME AND FUNCTION „ „ ● During address setting mode, indoor unit reject the any operation command from remote controller. Function number Refer to FUNCTION DETAILS MODE button Setting number - Start the function setting mode Refer to FUNCTION DETAILS - Changes the display digits FAN button START/STOP button...
FUNCTION SETTING „ „ (5) Press the “MODE” button to access the (6) Press the “ ” or the “ ” buttons to select function setting mode. the function number. Each time the “MODE” button is pressed, it switches between the one's place and the ten's place positions.
COMPLETION OF FUNCTION SETTING MODE „ „ (11) Press the “RESET” button. RESET After pressing the RESET button, please set the custom code again if b,c,d setting. SETTING UP EACH INDOOR UNIT „ „ Repeat steps (1) through to (11). Steps (1) through to (4) and (11) only need to carried out if the custom code is different to the factory setting of “A”.
Page 134
REMOTE CONTROLLER CUSTOM CODE SETTING „ „ In function setting, please change to the setting that custom code setting of Wireless remote controller is the same as indoor unit according to the following content when you change custom code setting of indoor unit. 1.
13-2-2. AR-RED1U SWITCHING SELECTION OF FUNCTION SETTING MODE „ „ " buttons. While holding these 2 (2) Press and hold the "POWERFUL" and "SET TEMP. buttons, press the "RESET" button. POWERFUL SET TEMP. ( RESET Function setting mode display - (01 - 131) -...
Page 136
BUTTON NAME AND FUNCTION „ „ ● During function setting mode, indoor unit reject the any operation command from remote controller. Function number Refer to FUNCTION DETAILS Setting number Refer to FUNCTION DETAILS MIN HEAT button POWERFUL button Changes the display digits Switches between the setting number (bottom line) and function number (top line)
Page 137
FUNCTION SETTING „ „ (3) Press the " " or the " " buttons to select the function number. Each time the "MIN HEAT" button is pressed, it switches between the one's place and the ten's place positions. Change digit Change digit (4) Press the "POWERFUL"...
Page 138
COMPLETION OF FUNCTION SETTING MODE „ „ (8) Press the "RESET" button. RESET SETTING UP EACH INDOOR UNIT „ „ Repeat steps (1) through to (8). Steps (1) through to (2) and (8) only need to carried out if the custom code is different to the factory setting of “A”.
Page 139
REMOTE CONTROLLER CUSTOM CODE SETTING „ „ In function setting, please change to the setting that custom code setting of Wireless remote controller is the same as indoor unit according to the following content when you change custom code setting of indoor unit. 1.
13-2-3. AR-REG1U SWITCHING SELECTION OF FUNCTION SETTING MODE „ „ " buttons. While holding these 2 (2) Press and hold the "POWERFUL" and "SET TEMP. buttons, press the "RESET" button. POWERFUL SET TEMP. ( RESET REG1U REG1U Function setting mode display - (01 - 136) -...
Page 141
BUTTON NAME AND FUNCTION „ „ ● During function setting mode, indoor unit reject the any operation command from remote controller. Function number Refer to FUNCTION DETAILS Setting number Refer to FUNCTION DETAILS MIN HEAT button POWERFUL button Changes the display digits Switches between the setting number (bottom line) and function number (top line)
Page 142
FUNCTION SETTING „ „ (3) Press the " " or the " " buttons to select the function number. Each time the "MIN HEAT" button is pressed, it switches between the one's place and the ten's place positions. Change digit Change digit (4) Press the "POWERFUL"...
Page 143
COMPLETION OF FUNCTION SETTING MODE „ „ (8) Press the "RESET" button. RESET REG1U SETTING UP EACH INDOOR UNIT „ „ Repeat steps (1) through to (8). Steps (1) through to (2) and (8) only need to carried out if the custom code is different to the factory setting of “A”.
Page 144
REMOTE CONTROLLER CUSTOM CODE SETTING „ „ In function setting, please change to the setting that custom code setting of Wireless remote controller is the same as indoor unit according to the following content when you change custom code setting of indoor unit. 1.
13-3. INDOOR UNIT (setting by wired remote controller) The function settings of the control of the indoor unit can be changed by this procedure ● „ according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. After the power is turned on, perform the “FUNCTION SETTING” according to the ●...
13-3-1. UTY-RNNUM SWITCHING SELECTION OF FUNCTION SETTING MODE „ „ (2) To activate the function setting mode, hold down the three buttons of SET TEMP. V, SET TEMP. Λ and FAN at the same time for 5 seconds or longer. Function setting mode initial display BUTTON NAME AND FUNCTION „...
Page 147
FUNCTION SETTING „ „ (3) Pressing the SET TIME < button or the SET TIME > button, to select the function number. Function number (4) Pressing the SET TEMP. V button or the SET TEMP. Λ button, to select the setting number.
Page 148
COMPLETION OF FUNCTION SETTING MODE „ „ (6) To clear the function setting mode and return to the regular display, hold down the three buttons of SET TEMP. V, SET TEMP. Λ and FAN at the same time. Normal mode display * If no key entry is made for 60 seconds, even though none of the above buttons is pressed, the function setting mode will automatically be cleared.
13-4. INDOOR UNIT (setting by simple remote controller) The function settings of the control of the indoor unit can be changed by this procedure ● „ according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. After the power is turned on, perform the “FUNCTION SETTING” according to the ●...
Page 150
SWITCHING SELECTION OF FUNCTION SETTING MODE „ „ (2) To activate the function setting mode, hold down the three buttons of SET TEMP. q , SET TEMP. p and FAN at the same time for 5 seconds or longer. Function setting mode initial display BUTTON NAME AND FUNCTION „...
Page 151
FUNCTION SETTING „ „ (3) Press the FAN button so that the “Function number” display flashes. Then, press either the SET TEMP. p button or the SET TEMP. q button to set up the function number. Function number (4) Press the FAN button so that the “Setting number” display flashes. Then, press either the SET TEMP.
Page 152
COMPLETION OF FUNCTION SETTING MODE „ „ (6) Press the three buttons of SET TEMP. p, SET TEMP. q and FAN at the same time for 5 seconds or longer. The function setting mode will be cleared and the regular display will be restored.
13-5. FUNCTION DETAILS Compact Wall Functions Slim duct Floor cassette mounted 1) Filter sign 2) Ceiling height 3) Outlet directions 4) Vertical airflow direction range control 5) Static pressure 6) Room temperature control for indoor unit sensor 7) Auto restart 8) Room temperature sensor switching 9) Remote controller custom code 10) External input control...
Page 154
3) Outlet directions Select the appropriate number of outlet directions according to the installation conditions. ( ... Factory setting) Function number Setting value Setting description 4-way 3-way 4) Vertical airflow direction range control In a concealed installation, change the setting to "Fixed" (02) to restrict the movement of the upper air outlet so that the airflow is only towards the horizontal direction.
Page 155
6) Room temperature control for indoor unit sensor Refer to Function 95, before performing this setting. Depending on the installed environment, correction of the room temperature sensor may be required. Select the appropriate control setting according to the installed environment. The temperature correction values show the difference from the Standard setting "00"...
Page 156
7) Auto restart Enable or disable automatic restart after a power interruption. ( ... Factory setting) Function number Setting value Setting description Enable Disable * Auto restart is an emergency function such as for power outage etc. Do not attempt to use this function in normal operation. Be sure to operate the unit by remote controller or external device.
Page 157
12) Indoor unit fan control for energy saving for cooling Enables or disables the power-saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation. ( ... Factory setting) Function number Setting value Setting description Disable ...
13-6. WIRED REMOTE CONTROLLER Prohibited Dual remote controller setting Prohibited Switch 1 °F / °C switch Prohibited Memory backup setting * Do not use DIP Switch 2 SWITCH POSITION „ „ Wired remote controller „ Front case (back side) DIP Switch 2 DIP Switch 1 (All switches fixed at OFF)
Page 159
DIP SWITCH 1 SETTING „ „ SW1 setting prohibited „ (u...Factory setting) Fixed at OFF Setting prohibited SW2 setting „ ● Dual remote controller setting Set the remote controller SW2 according to the following table. Indoor unit (u...Factory setting) Secondary Primary unit Number Remote controller cable...
Page 160
SW5 setting prohibited „ (u...Factory setting) Fixed at OFF Setting prohibited SW6 setting „ ● Memory backup setting (Wired remote controller only) Set to ON to use batteries for the memory backup. If batteries are not used, all of settings stored in memory will be deleted if there is a power failure.
DIP SWITCH SETTING „ „ SW1 setting prohibited „ (u...Factory setting) Fixed at OFF Setting prohibited SW2 setting „ ● Dual remote controller setting Set the remote controller SW2 according to the following table. Indoor unit (u...Factory setting) Secondary Primary unit Number Remote controller cable unit...
Page 163
SW5 setting prohibited „ (u...Factory setting) Fixed at OFF Setting prohibited SW6 setting prohibited „ (u...Factory setting) Fixed at OFF Setting prohibited - (01 - 159) -...
14-3. OTHERS LINE UP „ „ Indoor units Wall mounted Floor Type Model Compact ASU7RLF1 ASU7RLF ASU9RLS2 AGU9RLF Slim Duct ASU18RLF Cassette ASU9RLF1 ASU9RLF ASU12RLS2 AGU12RLF ASU24RLF ASU12RLF1 ASU12RLF ASU15RLS2 AGU15RLF Air outlet UTR-YDZB shutter plate Insulation kit for UTZ-KXGC ...
Page 167
PARTS „ „ Air outlet shutter plate Insulation kit for high humidity Models : UTR-YDZB Model : UTZ-KXGC Insulation For Compact Cassette type For Compact Cassette type Fresh air intake kit External control set Model : UTZ-VXAA Model : UTD-ECS5A ( x 1 ) ( x 2 ) ( x 1 )
Page 168
PARTS „ „ Communication kit Model : UTY-TWBXF For Wall Mounted (ASU9RLS2, ASU12RLS2, ASU15RLS2) type - (01 - 164) -...
INSTALLATION PRECAUTIONS 15-1. INDOOR UNIT INSTALLATION PRECAUTIONS Note: The information listed below are general precautions. Some models also include items that do not apply. PLACES WHERE USE PROHIBITED „ „ •Places where there is the danger of combustible gas leakage. •Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is generated •Places where there is a lot of oil splash and steam (kitchen, machinery room, etc.)
Page 170
[Installation precautions] Contents Countermeasures (Reference) When inside the When the indoor unit is installed where the inside of the ceiling Add heat insulating material to ceiling is high is 30°C (86°F) RH80% or greater, the dew point temperature the outside of the indoor unit temperature and of the outer perimeter may become higher than the cabinet cabinet.
Page 171
[Installation precautions] Contents Countermeasures (Reference) When installation When the wall mounting type was installed in a bedroom, living Plan installation of a model environment is room, or other quiet place, the sound of the refrigerant flow with external expansion valve. quiet may be sensed as noise and must be taken into accunt.
SPECIFICATIONS Model name AOU18RLXFZ Power source 1Ø 208/230V 60Hz Available voltage range 187-264V Number Connectable indoor unit Total capacity range 14,000 to 21,000 Btu/h non-Duct Duct Combination of indoor unit ASU9RLF1 x 2 ARU9RLF x 2 or ASU9RLF x 2 Btu/h 18,000 18,000...
DIMENSIONS MODEL : AOU18RLXFZ „ „ Unit: in. (mm) Top view 1-9/16 1-1/4 35-7/16 (900) (40) (31) 13 (330) (12) 15-3/4 (400) Front view Side view 25-9/16 (650) (12) 4-Ø1/2 (Ø12) Bottom view 1-5/8 Drain cap mounting places Drain pipe mounting places (41) - (02 - 02) -...
Page 176
INSTALLATION PLACE „ „ Unit: in. (mm) When there are obstacles at When there are obstacles at When there are obstacles at the the back or front sides. the back, side(s), and top. back, side with the installation of more than one unit. *4 (100) 4 (100) 10 (250)
CAPACITY TABLE 5-1. COMBINATIONS MODEL : AOU18RLXFZ „ „ Cooling „ Rated capacity Maximum capacity Combination of indoor unit for each indoor unit for each indoor unit Total capacity [kBtu/h] Input power [kW] Type of [kBtu/h] [kBtu/h] indoor unit Room 1 Room 2 Total Room 1 Room 2...
5-3. HEATING CAPACITY This table is created using the maximum capacity. MODEL : AOU18RLXFZ „ „ Indoor unit : 7,000Btu „ Indoor temperature 60°FDB 65°FDB 70°FDB 75°FDB 78°FDB (°FDB) (°FWB) 8.16 1.06 7.90 1.09 7.64 1.12 7.37 1.15 7.21 1.17 9.31 1.13 9.02...
ADDITIONAL CHARGE CALCULATION MODEL : AOU18RLXFZ „ „ Refrigerant type R410A lbs. oz. 4 lbs. 14 oz. Refrigerant amount 2,200 Refrigerant charge „ 98 or less 164 (MAX.) Total pipe length 30 or less 50 (MAX.) 0.21 oz./ft. 20g/m lbs. oz. 7.1 oz.
ELECTRIC CHARACTERISTICS Model name AOU18RLXFZ Voltage 208 / 230 ~ Power supply Frequency Starting current MAX. CKT. BKR *1) Wiring spec. Power cable *1) Wiring spec. : selected sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005) MCA: Min Circuit Amp(Calculation based on UL1995) MAX.
SAFETY DEVICES Model Protection form AOU18RLXFZ 250V 3.15A Current fuse (MAIN PCB) 250V 5A Circuit protection Current fuse 250V 10A (NEAR THE TERMINAL) OFF: 302 ± 27 °F OFF: 150 ± 15 °C Fan motor protection Temperature Thermistor ON: 248 ± 27 °F ON: 120 ±...
INSTALLATION PRECAUTIONS 12-1. OUTDOOR UNIT INSTALLATION PRECAUTIONS Note: The information listed below are general precautions. Some models also include items that do not apply. PLACES WHERE USE PROHIBITED „ „ • Places where there is the danger of combustible gas leakage •...
Page 200
3. OUTDOOR UNIT (3 ROOMS TYPE) MULTI TYPE : AOU24RLXFZ DTR_AO075E_08 2015.02.19...
SPECIFICATIONS Model name AOU24RLXFZ Power source 1Ø 208/230V 60Hz Available voltage range 187-264V Number 2 to 3 Connectable indoor unit Total capacity range 14,000 to 27,000 Btu/h non-Duct ASU9RLF1 + ASU7RLF1 x 2 Duct Combination of indoor unit ARU12RLF x 2 ASU9RLF + ASU7RLF x 2 Btu/h 22,000...
DIMENSIONS MODEL : AOU24RLXFZ „ „ Unit: in. (mm) Top view 1-9/16 1-1/4 35-7/16 (900) (40) (31) 13 (330) (12) 15-3/4 (400) Front view Side view 25-9/16 (650) (12) 4-Ø1/2 (Ø12) Bottom view 1-5/8 Drain cap mounting places Drain pipe mounting places (41) - (03 - 02) -...
Page 204
INSTALLATION PLACE „ „ Unit: in. (mm) When there are obstacles at When there are obstacles at When there are obstacles at the the back or front sides. the back, side(s), and top. back, side with the installation of more than one unit. *4 (100) 4 (100) 10 (250)
CAPACITY TABLE 5-1. COMBINATIONS MODEL : AOU24RLXFZ „ „ Cooling „ Rated capacity Maximum capacity Total capacity Combination of indoor unit for each indoor unit for each indoor unit Input power [kW] Type of [kBtu/h] [kBtu/h] [kBtu/h] indoor unit Room 1 Room 2 Room 3 Total Room 1 Room 2 Room 3 Room 1 Room 2 Room 3 Min.
5-3. HEATING CAPACITY This table is created using the maximum capacity. MODEL : AOU24RLXFZ „ „ Indoor unit : 7,000Btu „ Indoor temperature 60°FDB 65°FDB 70°FDB 75°FDB 78°FDB (°FDB) (°FWB) 8.16 1.06 7.90 1.09 7.64 1.12 7.37 1.15 7.21 1.17 9.31 1.13 9.02...
ADDITIONAL CHARGE CALCULATION MODEL : AOU24RLXFZ „ „ Refrigerant type R410A lbs. oz. 4 lbs. 14 oz. Refrigerant amount 2,200 Refrigerant charge „ 98 or less 164 (MAX) Total pipe length 30 or less 50 (MAX) 0.21 oz./ft. 20g/m lbs. oz. 7.1 oz.
ELECTRIC CHARACTERISTICS Model name AOU24RLXFZ Voltage 208 / 230 ~ Power supply Frequency Starting current MAX. CKT. BKR *1) Wiring spec. Power cable *1) Wiring spec. : selected sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005) MCA: Min Circuit Amp(Calculation based on UL1995) MAX.
SAFETY DEVICES Model Protection form AOU24RLXFZ 250V 3.15A Current fuse (MAIN PCB) 250V 5A Circuit protection Current fuse 250V 10A (NEAR THE TERMINAL) OFF: 302 ± 27°F OFF: 150 ± 15 °C Fan motor protection Temperature Thermistor ON: 248 ± 27 °F ON: 120 ±...
INSTALLATION PRECAUTIONS 12-1. OUTDOOR UNIT INSTALLATION PRECAUTIONS Note: The information listed below are general precautions. Some models also include items that do not apply. PLACES WHERE USE PROHIBITED „ „ • Places where there is the danger of combustible gas leakage •...
Page 242
4. OUTDOOR UNIT (4 ROOMS TYPE) MULTI TYPE : AOU36RLXFZ1 DTR_AO207E_01 2015.02.19...
SPECIFICATIONS Model name AOU36RLXFZ1 Power source 1Ø 208/230V 60Hz Available voltage range 187-264V Number 2* to 4 Connectable indoor unit Total capacity range 27,000 to 39,000 Btu/h Non-Duct Duct Combination of indoor unit ASU9RLF1 x 4 ARU9RLF x 4 Btu/h 35,200 35,200 35,200...
DIMENSIONS MODEL : AOU36RLXFZ1 „ „ Unit: in. (mm) Top view 1-9/16 1-1/4 35-7/16 (900) (40) (31) 13 (330) (12) 15-3/4 (400) Side view Front view 25-9/16 (650) 3/16 (5) Bottom view 1/2 (12) 4-Ø1/2 (Ø12) 1-5/8 (41) - (04 - 02) -...
Page 246
INSTALLATION PLACE „ „ Unit: in. (mm) When there are obstacles at When there are obstacles at When there are obstacles at the the back or front sides. the back, side(s), and top. back, side with the installation of more than one unit. 4 (100) *4 to 12 10 (250)
CAPACITY TABLE 5-1. COMBINATIONS MODEL : AOU36RLXFZ1 „ „ Cooling „ Rated capacity Maximum capacity Total capacity Combination of indoor unit for each indoor unit for each indoor unit Input power [kW] [kBtu/h] Type of [kBtu/h] [kBtu/h] indoor unit Room Room Room Room...
Page 250
Heating „ Rated capacity Maximum capacity Total capacity Combination of indoor unit for each indoor unit for each indoor unit Input power [kW] [kBtu/h] Type of [kBtu/h] [kBtu/h] indoor unit Room Room Room Room Room Room Room Room Room Room Room Room Total...
5-3. HEATING CAPACITY MODEL : AOU36RLXFZ1 „ „ This table is created using the maximum capacity. Indoor unit : 7,000Btu „ Indoor temperature 60°FDB 65°FDB 70°FDB 75°FDB 78°FDB (°FDB) (°FWB) 7.26 1.21 7.08 1.24 6.91 1.26 6.74 1.29 6.56 1.31 8.83 1.23 8.62...
ADDITIONAL CHARGE CALCULATION MODEL : AOU36RLXFZ1 „ „ Refrigerant type R410A lbs. oz. 7 lbs. 1 oz. Refrigerant amount 3,200 Refrigerant charge „ ●3 or 4 indoor units are connected 164 or less 230 (MAX.) Total pipe length 50 or less 70 (MAX.) 0.22 oz./ft.
ELECTRIC CHARACTERISTICS Model name AOU36RLXFZ1 Voltage 208 / 230 ~ Power supply Frequency 24.6 Starting current 17.1 MAX. CKT. BKR *1) Wiring spec. Power cable *1) Wiring spec. : selected sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005) MCA: Min Circuit Amp(Calculation based on UL1995) MAX.
SAFETY DEVICES Model Protection form AOU36RLXFZ1 250V 3.15A Current fuse (MAIN PCB) 250V 5A Circuit protection Current fuse 250V 10A (NEAR THE TERMINAL) OFF: 251 ± 16 °F OFF: 122 ± 9 °C Fan motor protection Temperature Thermistor ON: 240 °F ON: 116 °C...
OPTIONAL PARTS Exterior Parts name Model No. Summary For 2rooms combination system It can exchange liquid pipe size Ø1/4 in. (Ø6.35mm) for Ø3/8 in. K9FZ1818 (Ø9.52mm), and Ø3/8 in. (Ø9.52mm) Adapter kit (UTP-MU36A2) for Ø1/2 in. (Ø12.70mm) If you choice 2 indoor units system "18,000 Btu + 18,000 Btu", then you need this kit.
Page 302
2 ROOMS COMBINATION (WITH OPTIONAL PARTS K9FZ1818) „ „ Size of piping „ Indoor unit B (18,000Btu) Outdoor unit Indoor unit A (18,000Btu) Gas pipe : Liquid pipe : Ø1/2 in. (Ø12.70 mm) Ø3/8 in.(Ø9.52 mm) How to use an adapter (optional parts K9FZ1818) „...
INSTALLATION PRECAUTIONS 13-1. OUTDOOR UNIT INSTALLATION PRECAUTIONS Note: The information listed below are general precautions. Some models also include items that do not apply. PLACES WHERE USE PROHIBITED „ „ • Places where there is the danger of combustible gas leakage •...