5-3. Cooling Capacity
Indoor Unit
SAP – K91AHA
Outdoor Unit
SAP – C91AHA
240V Single Phase 50Hz
EVAPORATOR
ENT. TEMP. °C
W.B.
Rating conditions (#Mark) are
RATING CAPACITY
AIR FLOW RATE
D.B.
TC
CM
21
SHC
15
23
SHC
25
SHC
27
SHC
29
SHC
31
SHC
TC
CM
21
SHC
17
23
SHC
25
SHC
27
SHC
29
SHC
31
SHC
TC
CM
21
SHC
19
23
SHC
25
SHC
27
SHC
29
SHC
31
SHC
TC
CM
23
SHC
21
25
SHC
27
SHC
29
SHC
31
SHC
TC
CM
23
25
SHC
27
SHC
29
SHC
31
SHC
TC :
Total Cooling Capacity (kW)
SHC : Sensible Heat Capacity (kW)
CM : Compressor Input (kW)
Outdoor Ambient Temp. 35°C D.B.
Indoor Unit Entering Air Temp. 27°C D.B. / 19°C W.B.
2.50 kW
3
430 m
/h
CONDENSER
OUTDOOR AMBIENT TEMP. °C
20
25
30
2.52
2.41
2.30
0.70
0.76
0.81
1.71
1.65
1.59
1.92
1.86
1.80
2.13
2.07
2.01
2.34
2.28
2.22
2.52
2.41
2.30
2.52
2.41
2.30
2.70
2.59
2.47
0.72
0.78
0.83
1.49
1.43
1.38
1.70
1.64
1.59
1.91
1.85
1.80
2.12
2.06
2.01
2.33
2.27
2.22
2.54
2.48
2.43
2.88
2.75
2.63
0.74
0.80
0.86
1.26
1.21
1.15
1.47
1.42
1.36
1.68
1.63
1.57
1.89
1.84
1.78
2.10
2.05
1.99
2.31
2.26
2.20
3.05
2.92
2.78
0.76
0.82
0.88
1.24
1.19
1.13
1.45
1.40
1.34
1.66
1.61
1.55
1.87
1.82
1.76
2.08
2.03
1.97
3.23
3.09
2.95
0.78
0.84
0.90
1.21
1.16
1.10
1.42
1.37
1.31
1.63
1.58
1.52
1.84
1.79
1.73
17
35
40
43
2.19
2.06
1.89
0.87
0.94
1.01
1.54
1.47
1.40
1.75
1.68
1.61
1.96
1.89
1.82
2.17
2.06
1.89
2.19
2.06
1.89
2.19
2.06
1.89
2.35
2.21
2.03
0.89
0.96
1.03
1.32
1.26
1.18
1.53
1.47
1.39
1.74
1.68
1.60
1.95
1.89
1.81
2.16
2.10
2.02
2.35
2.21
2.03
# 2.50
2.35
2.16
0.92
0.99
1.06
1.10
1.03
0.96
1.31
1.24
1.17
1.52
1.45
1.38
1.73
1.66
1.59
1.94
1.87
1.80
2.15
2.08
2.01
2.65
2.49
2.29
0.95
1.02
1.09
1.08
1.02
0.94
1.29
1.23
1.15
1.50
1.44
1.36
1.71
1.65
1.57
1.92
1.86
1.78
2.78
2.60
2.42
0.97
1.05
1.12
1.04
0.98
0.91
1.25
1.19
1.12
1.46
1.40
1.33
1.67
1.61
1.54