6. MULTIPLE REMOTE CONTROL DISPLAY
You can control several units with a multiple remote control display, by
wiring an optional multiple display adapter (PAC-SA88HA-E) with relays
and lamps on the market.
How to wire
(1) Connect the multiple display adapter to the connector CN51 on the
indoor controller board.
(2) Wire three of the five wires from the multiple display adapter as shown
in the figure below.
<Wiring >
GREEN
5
CN51
YELLOW
ORANGE
1
connector(5P)
RED
Electrical insulation is needed.
BROWN
Optional multiple display
adapter
The maximum distance between
indoor board and relay is 33ft.
<System>
3wires
Power
3wires
supply
3wires
No.1 unit
2wires
Multiple remote control
Remote
ON-OFF display
(Field supply)
controller
(Operation check)
<Wiring diagram>
RL-1
Power
GL-1
supply
RL-2
GL-2
RL-3
GL-3
Multiple Remote Control Display

7. AUTO RESTART FUNCTION

By setting the dip switch SW1-8 to ON, the air conditioner can be started/stopped by power supply ON/OFF.
If the air conditioner is OFF before the power failure, it will not start operation by power restore.
•This function is mainly to emergency performance when the power supply stops temporarily. Therefore, since the protec-
tion function (for example, clank case heater and prevention from restarting in 3 minutes, etc.) of the device is not operat-
ed, this function should not be used mostly.
8. TIMER OPERATION OR THE OPERATION BY AN EXTERNAL SIGNAL
<Wiring>
A
B
Brown
Red
For remote control, connect the optional timer adapter (PAC-SA89TA-E)
X2
X2
X1
X1
Wiring at the actual place
No.2 unit
Remote
Relay box
controller
(Field supply)
cable
Remote
Remote
controller
controller
X1-1
X2-1
X1-2
X2-2
X1-3
X2-3
A
B
Brown
Red
Orange
Remote controller
Orange
GL
RL
Power
supply
No.3 unit
1
X1-1
X2-1
5
1
X1-2
X2-2
5
1
X1-3
X2-3
5
Relay box
A : an optional timer adapter
B : a single-throw switch
Remote controller
54
Indoor controller board
CN51
[Notes on Signs]
X1:Relay (for operation lamp)
X2:Relay (for check lamp)
RL:Operation Lamp
GL:Check Lamp
[Field supplied parts]
Relays:12V DC with rated coil power
consumption below 0.9W.
Lamps:Matching to power supply voltage.
Multiple remote
controller adapter
No.1 unit
No.2 unit
No.3 unit
connect to
the connector CN51
CN51