FOllOw inStRuctiOnS MaY ReSult in PROPeRtY daMage, bOdilY injuRY, OR even death. FOR uSe in the u.S. and canada. Suitable FOR inStallatiOn in MObile hOMeS. iF thiS haRMan StOve iS nOt PROPeRlY inStalled, a hOuSe FiRe MaY ReSult. FOR YOuR SaFetY, FOllOw inStallatiOn diRectiOnS.
Page 3
76mm min 3" min 9"(228mm) 3-90-04301R14_09/12 P43 Pellet Stove...
The P43 Pellet Stove has huge features in a small package, giving you 0 to 43,000 BTU when you need it, automatically. You basically need to set your desired room temperature and fill the hopper. With the P43 you will notice even heat throughout your zone and a level of convenience you never thought possible.
Page 5
OR OtheR cOncealed SPace, a FlOOR, OR a ceiling. inStallatiOn and RePaiR OF thiS haRMan StOve ShOuld be dOne cautiOn bY a QualiFied SeRvice PeRSOn. we RecOMMend that the StOve dO nOt cOnnect tO OR uSe in...
The P43 is bolted (1/4 x 1" hex head bolts) to the skid to prevent movement during shipping. To free the stove from the skid you must remove the hold-down bolts in the rear of the pedestal base.
Page 7
Measurement "K" is measured from waRning the glass in the US ONLY the StRuctuRal integRitY OF the ManuFactuRed hOMe FlOOR, wall, and ceiling/ROOF MuSt be Maintained. canada dO nOt inStall in SleePing ROOM. loor protector 3-90-04301R14_09/12 P43 Pellet Stove...
Page 8
(if in canada) measured from the horizontal center-line of the regulator. = Venting Terminal = Air Supply Inlet = Area where termination is not permitted P43 Pellet Stove 3-90-04301R14_09/12...
Page 9
OR ROOF SPace, hearth & home technologies strongly recommends clOSet OR SiMilaR cOncealed SPace, attaching outside air in all installations, especially lower level and main floor locations. FlOOR , OR ceiling. ReFeRence lOcal building cOdeS FOR detailS. 3-90-04301R14_09/12 P43 Pellet Stove...
Page 10
To install outside air use 2 3/8" I.D. non-combustible flex pipe. There is a break-away hole on the rear Direct Vent Wall Passthrough Kit panel of the P43 stove which must be removed before (part #1-00-677077) connecting the flex pipe. The pipe should be run outside and terminate to the side or below the vent pipe outlet so the flue outlet is more than 12"...
Page 11
(such as grass, leaves, etc.) at least 3 feet away from the flue outlet on the outside of the building. 3 Ft. 12" min. wall to outlet Fig. 9 to combustibles 3-90-04301R14_09/12 P43 Pellet Stove...
The connector pipe should extend through the smoke chamber to the base or into the first flue tile. Be sure to design the venting so that it can be easily cleaned. Fig. 11 P43 Pellet Stove 3-90-04301R14_09/12...
Page 13
The pipe or liner inside the chimney should be 4" diameter. In this method a cap should also be installed on the chimney to keep out rain. Fig. 13 3-90-04301R14_09/12 P43 Pellet Stove...
Page 14
#8 installing through the ceiling Through the ceiling vent, follow PLvent manufacturers recommendations when using wall and ceiling pass through. note: do not place joints within wall pass- throughs. 12" min. wall to outlet Fig. 16 P43 Pellet Stove 3-90-04301R14_09/12...
P43 automatic ignition eSP control Feed adjuster Sets the maximum Power Light feed rate. Indicates power to the control. Test Runs all motors at full speed for one minute Status Light to check operation. Will be lit in either stove...
Page 16
P43 automatic ignition / Operation The P43 is a fully automatic stove that features two Room temperature Mode operating modes; Stove Temperature Mode and Room Temperature Mode. In Stove Temperature Mode, you select a burn rate and the stove will remain at the same burn rate regardless of the room temperature.
Page 17
P43 automatic ignition / Operation Stove temperature Mode out. The fire will not go out immediately and may take In the Stove Temperature Mode and with the igniter more than an hour to fully shut down. toggle switch in the Auto position, the stove will light...
Page 18
P43 automatic Start up Starting First Fire igniter Switch to"autO"(up position) Make sure the unit is plugged into a 120 VAC, 60 HZ electrical source. The power light should be the only light lit. SeeHint #7. Fig. 17 nOtice: be sure there is no unburned fuel Flame Guide 1"...
P43 Manual ignition / Operation The P43 Pellet Stove is capable of manual operation. This also allows the operator to manually control operation during an emergency (i.e. igniter failure, when using a 502H battery backup, as opposed to the 512H, or when using certain generators.) The unit can be switched between "AUTO"...
Page 20
P43 Manual Start up Starting First Fire igniter Switch to"Manual" (down position) Fig. 20 Make sure the unit is plugged into a 120 VAC, 60 HZ electrical source. The power light should be the only light lit. Fig. 19 nOtice: be sure there is no unburned fuel See Hint #7.
1. Plug unit into a 120VAC, 60 HZ outlet. for firebox tightness, gasket leakage, motor operation and igniter operation. The P43 is then factory set at a 2. Close the hopper lid, front view door, and the ash mid-point adjustment and in most cases will not need pan.
Before re-using the appliance, have it, and the venting system thoroughly inspected and replace any damaged components. The glass in your Harman stove is a special 5mm ceramic glass. •...
Page 23
4. Scrape burnpot with flat end of scraper provided with Blower the stove. Inspect the holes on the burnpot surface. Wheel See Fig. 33. 5. Open burn pot clean-out. Clean fly ash from burn pot and replace cover. Blower Cover Latch Fig 27 3-90-04301R14_09/12 P43 Pellet Stove...
Page 24
The stove should be cleaned after damage ESP probe each ton of pellets (50 bags) and the venting system when cleaning with inspected and cleaned after each heating season. brush. Probe Fig. 31 Fig. 33 P43 Pellet Stove 3-90-04301R14_09/12...
Page 25
P43 Maintenance - burn Pot burn Pot cleaning and Maintenance 1. Scrape the top holed surface and sides of the burn pot.(Fig 33) It is not necessary to completely remove all material from the burn pot. The excess will be pushed out during the next use.
P43 Maintenance - cleaning the Feeder body Pellet fines may accumulate in the feeder body over a period of time; therefore, a yearly inspection and cleaning of this area must be performed. To clean out fines: 5/16" Hex Head 5/16" Hex Head Screws (2 on 1.
4. The holes in the burnpot may be getting filled with and all others at 3% or more. ash or carbon buildup. The P43 is capable of burning all 3 categories of pellets 5. Combustion blower fan blades may need cleaned. due to a patented feeder and burn pot system.
Page 28
Flue Size 3 inch Outside Air Size 2 3/8" I.D. inch Fuse Rating 6 amp P43 wiring diagram HARMAN P43/P61A/P68 PELLET STOVE WIRING DIAGRAM MALE/FEMALE CONNECTIONS BROWN WHITE GREEN WIRE IS GROUND REMOTE SENSOR PORTS 6 AMP GLASS FUSE BONDED TO STOVE BODY...
This will allow the swell latch of the hopper extension to fully expand to the bottom side of the hole for a proper seal. 3-90-04301R14_09/12 P43 Pellet Stove...
Damp pellet fuel could turn back into sawdust which does not flow properly through the feed system. P43 Pellet Stove 3-90-04301R14_09/12...
Page 31
Addendum for Burning Corn and Pellet Fuel Mixture Harman pellet burning, free-standing stoves and inserts have been tested to ASTM E1509 for burning shelled corn in a mixture with wood pellets. The listing approves up to a 50% corn and 50% pellet mixture. Different mixtures of corn will have distinctively different burn characteristics depending upon moisture content and variety.
Page 32
Contact your dealer if you have questions about UPS compatibility with your appliance. harman Surefire 512h battery back-up The 512H connects to a 12 volt deep cycle battery that will run your appliance for up to eight (8) hours. It includes a trickle charge feature that keeps your battery charged when power is available.
Page 33
1 year Burners, logs and refractory years Limited 3 years Firebox and heat exchanger Lifetime All replacement parts 90 Days beyond warranty period See conditions, exclusions, and limitations on next page. 4021-645C 12-29-10 Page 1 of 2 3-90-04301R14_09/12 P43 Pellet Stove...
Page 34
THE EXTENT PROVIDED BY LAW, HHT MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY SPECIFIED HEREIN. THE DURATION OF ANY IMPLIED WARRANTY IS LIMITED TO DURATION OF THE EXPRESSED WARRANTY SPECIFIED ABOVE. 4021-645C 12-29-10 Page 2 of 2 P43 Pellet Stove...
Page 36
P43 Pellet Service Parts beginning Manufacturing date: n/a ending Manufacturing date: active IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement parts for your appliance please provide model number and serial number. All parts listed Stocked in this manual may be ordered from an authorized dealer.
Page 37
P43 Pellet Service Parts beginning Manufacturing date: n/a ending Manufacturing date: active #2 Feeder assembly 2.12 2.15 2.16 2.14 2.13 2.11 2.10 IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement parts for your appliance please provide model number and serial number. All parts listed Stocked in this manual may be ordered from an authorized dealer.
Page 38
P43 Pellet Service Parts beginning Manufacturing date: n/a ending Manufacturing date: active IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement parts for your appliance please provide model number and serial number. All parts listed Stocked in this manual may be ordered from an authorized dealer.
Page 39
Service & Maintenance log Date Of Service Performed By Description Of Service 3-90-04301R14_09/12 P43 Pellet Stove...
Page 40
At Harman, we build each product to a standard, not a price. This powerful heating appliance boasts uncompromising attention to detail and helps preserve our planet by using environmentally responsible fuels. (Signature of Boxer) Your premium quality hearth product designed and assembled by the experienced and skilled members at Harman in Halifax, PA, USA.