CERTIFIED UNDER CANADIAN AND AMERICAN NATIONAL STANDARDS: ANSI Z21.50 CSA 2.22 FOR VENTED GAS FIREPLACE.
GD19N

NATURAL GAS

GD19P
PROPANE
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI/CSA METHODS.

SAFETY INFORMATION

WARNING
!
If the information in these instructions are
not followed exactly, a fire or explosion
may result causing property damage,
personal injury or loss of life.
- Do not store or use gasoline or other
flammable vapors and liquids in the vicinity
of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do
not use any phone in your building.
Immediately call your gas supplier from
a neighbour's phone. Follow the gas
supplier's instructions.
If you cannot reach your gas supplier,
call the fire department.
-
Installation
and
performed by a qualified installer, service
agency or the supplier.
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 4Y8 Canada • (705)721-1212 • fax(705)722-6031
$10.00
NorthlineExpress.com
INSTALLER: LEAVE THIS MANUAL WTIH THE APPLIANCE.
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
OPERATION INSTRUCTIONS
service
must
be
www.napoleonfireplaces.com • ask@napoleon.on.ca
http://www.northlineexpress.com
INSTALLATION
1
AND
W415-0612 / C / 01.25.08
Toll-Free 1-866-667-8454

Advertisement

Table of Contents
loading

Summary of Contents for Napoleon Vittoria GD19N

  • Page 1: Natural Gas

    Installation service must performed by a qualified installer, service agency or the supplier. Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON L4M 4Y8 Canada • (705)721-1212 • fax(705)722-6031 www.napoleonfireplaces.com • ask@napoleon.on.ca $10.00 W415-0612 / C / 01.25.08 NorthlineExpress.com http://www.northlineexpress.com...
  • Page 2: Table Of Contents

    TABLE of CONTENTS PG 2-5 INTRODUCTION BLOWER INSTALLATION Warranty NIGHT LIGHT REPLACEMENT General Instructions 26-27 FINISHING General Information Care of Glass and Plated Parts Glass Door Installation and Removal Dimensions Log Placement Logo Placement 5-15 VENTING Control Functions Venting Lengths and Air Terminal Locations Typical Vent Installations WIRING DIAGRAM Special Vent Installations...
  • Page 3: Warranty

    NAPOLEON® warrants its stainless steel burners against defects in workmanship and material for life, subject to the following condi- tions: During the fi rst 10 years NAPOLEON® will replace or repair the defective parts at our option free of charge. From 10 years to life, NAPOLEON®...
  • Page 4: General Instructions

    Provided that the clearance to combustibles are achieved, The fireplace and its individual shutoff valve must be the most desirable and benefi cial location for a Napoleon® disconnected from the gas supply piping system during any fi replace is in the centre of a building, thereby allowing pressure testing of that system at test pressures in excess the most effi...
  • Page 5: Dimensions

    DIMENSIONS FIGURE 1b FIGURE 1c FIGURE 1a 7” DIA. 4” DIA. ” ” ” ” ” LINE ACCESS 12” ” ELECTRICAL 13” ” ” ACCESS FIGURE 1e FIGURE 1d FIGURE 1f ” ” 9” ” 7” DIA. 4” DIA. 5” ”...
  • Page 6 VENTING LENGTHS AND AIR TERMINAL LOCATIONS CONTINUED When using Wolf Steel venting components, use only For optimum fl ame appearance and fi replace performance, approved Wolf Steel rigid / fl exible components with the keep the vent length and number of elbows to a minimum. GD222, or following termination kits:Wall Terminal Kit The air terminal must remain unobstructed at all times.
  • Page 7: Typical Vent Installations

    TYPICAL VENT INSTALLATIONS REAR EXIT TOP EXIT FIGURE 3a FIGURE 2a 16” 16” MINIMUM MINIMUM 35 FT MAXIMUM 35 FT MAXIMUM 3 FT MINIMUM 3 FT MINIMUM FIGURE 2b FIGURE 3b 20" MAXIMUM 24" MAXIMUM 10" MINIMUM " MINIMUM PLUS RISE* "...
  • Page 8: Minimum Air Terminal Location Clearances

    MINIMUM AIR TERMINAL LOCATION CLEARANCES FIGURE 6 W415-0612 / C / 01.25.08 NorthlineExpress.com http://www.northlineexpress.com Toll-Free 1-866-667-8454...
  • Page 9 W415-0612 / C / 01.25.08 NorthlineExpress.com http://www.northlineexpress.com Toll-Free 1-866-667-8454...
  • Page 10 DEFINITIONS ELBOW VENT LENGTH VALUES For the following symbols used in the venting calculations feet inches 1° 0.03 and examples are: > - greater than 15° 0.45 > - equal to or greater than 30° 11.0 < - less than 45°...
  • Page 11 TOP EXIT / HORIZONTAL TERMINATION ) > (V Example 2: = 6 ft FIGURE 9 = 3 ft = 5 ft = 3 + 5 = 8 ft = .03(two 90° elbows - 90°) = .03(180° - 90°) = 2.7 ft Simple venting confi...
  • Page 12 REAR EXIT / HORIZONTAL TERMINATION 90° Example 4: ) < (V Simple venting confi guration (only two 90° elbows) 90° FIGURE 13 90° FIGURE 12 See graph to determine the required vertical rise V for the required horizontal run H = 9 ft = 6 ft = 9 + 6 = 15 ft...
  • Page 13 REAR EXIT / HORIZONTAL TERMINATION ) > (V Example 5: 90° Simple venting confi guration 90° (only two 90° elbows) 90° 45° FIGURE 14 FIGURE 15 90° See graph to determine the required vertical rise V for the required horizontal run H = 4 ft = 1.5 ft = 4 + 1.5 = 5.5 ft...
  • Page 14 TOP OR REAR EXIT VERTICAL TERMINATION ) < (V Example 6: 90° FIGURE 17 90° FIGURE 16 90° 90° ple venting confi gurations = 3 ft See graph to determine the required vertical rise V for the = 6 ft required horizontal run H = 8 ft = 3 + 6 + 8 = 17 ft...
  • Page 15 Example 7: ) > (V = 2 ft = 1 ft Simple venting confi gurations = 1.5 ft = 2 + 1 + 1.5 = 4.5 ft = 6 ft = 2 ft = 6 + 2 = 8 ft = .03(four 90°...
  • Page 16: Top Exit Conversion

    TOP EXIT CONVERSION In order to convert the venting confi guration from a rear exit to a top exit, remove the components as illustrated: When reinstalling in the alternate position: Check gaskets for tears, replace if necessary to ensure a proper seal. FIGURE 18 Outer Top 7”...
  • Page 17: Installation

    American Metal Amerivent, or Wolf Steel rigid or Installation kits for various roof pitches are available from your Napoleon® dealer. See Accessories to order the specifi c fl exible vent components. For safe and proper operation of the fi replace, kit required.
  • Page 18: Using Flexible Vent Components

    USING FLEXIBLE VENT COMPONENTS WARNING Use only approved fl exible vent pipe kits marked: FIGURES 22a&b ELBOW Do not allow the 4" flexible vent pipe to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1 1/4” air gap between the 4" and 7"...
  • Page 19: Fireplace Vent Connection

    W615-0033 every 3 feet on either side of each elbow to maintain the minimum 1¼" clearance between the 7" rigid vent pipe and 4" rigid vent pipes. Use Napoleon® support ring assembly W010-0370 or equivalent noncombustible strapping to maintain the minimum clearance to combustibles for both vertical and horizontal runs.
  • Page 20: Restricting Vertical Vents

    6. Remove nails from the shingles, above and to the EXTENDED HORIZONTAL AND CORNER sides of the chimney. Place the fl ashing over the air terminal AIR TERMINAL INSTALLATION connector and slide it underneath the sides and upper edge FIGURE 30 1.
  • Page 21: Mobile Home Installation

    The mobile home appliance is fi eld convertible between CODE in Canada or the ANSI/NFPA 70-1996 NATIONAL Natural Gas (NG) and Propane (LP). ELECTRICAL CODE in the United States. To convert from one gas to another consult your Napoleon ® dealer/distributor. CABLE...
  • Page 22: Framing

    FRAMING Minimum clearance to combustible construction from It is best to frame your fi replace after it is positioned and the vent fi replace and vent surfaces: system is installed. Frame to local building codes. NOTE: In order to avoid the possibility of exposed insulation Combustible Framing: or vapour barrier coming in contact with the fi...
  • Page 23: Minimum Mantel And Enclosure Clearances

    MINIMUM MANTEL AND ENCLOSURE CLEARANCES Mantel clearance can vary according to the mantel depth. COMBUSTIBLE NON-COMBUSTIBLE Use the graph to help evaluate the clearance needed. Combustible materials must be installed fl ush with the front BRICK of the fi replace but must not cover any of the black face-area 6”...
  • Page 24 FRONT FACING AND INSET KIT INSTALLATION FIGURE 48 FIGURE 45 Hook the bottom of the front facing on the bottom lip of the fi rebox. Pivot the front facing against the fi rebox and insert the head of the turn button through the slot in the front facing.
  • Page 25: Blower Installation

    BLOWER INSTALLATION ELECTRICAL INSTALLATION TO BE DONE BY A QUALIFIED INSTALLER and must be connected and grounded in accordance with local codes. In the absence of local codes, use the current CSA C22.1 in Canada or the CANADIAN ELECTRICAL CODE current ANSI/NFPA 70 in the United States.
  • Page 26: Finishing

    FINISHING GLASS DOOR INSTALLATION AND REMOVAL Before the glass door can be removed, the optional front must be removed. The glass door is secured to the top front edge of the fi rebox and retained by the bottom. 1. Unlatch door 2.
  • Page 27: Logo Placement

    Blocked burner ports can cause an incorrect fl ame pattern, carbon deposits and delayed ignition. Phazer logs glow when exposed to direct fl ame. Use only certifi ed "glowing embers" and Phazer logs available from your Napoleon® dealer. LOGO PLACEMENT Remove the backing of the FIGURE 61 logo supplied and place on "...
  • Page 28: Wiring Diagram

    WIRING DIAGRAM The main burner and Night Light switch is located behind Route 2-strand (solid core) wire through the electrical hole lower access panel. For ease of accessibility, optional re- located at the bottom left side of the unit. Connect the wires mote wall switches may be installed in a convenient location from the main burner wall switch to the two corresponding for both burner and light operation.
  • Page 29: Operation / Maintenance

    A 5-10 second total light-up period is satisfactory. If ignition takes and liquids. The fl ow of combustion and ventilation air must not be longer, consult your Napoleon® dealer/distributor. obstructed. 7. Check that the door gasketing is not broken or missing.
  • Page 30: Adjustments

    ADJUSTMENTS PILOT INJECTOR AND ORIFICE REPLACEMENT 1. Turn off the electrical NOTE: Check and adjust, if necessary, the primary air FIGURE 64 and gas supply to the ” for propane and " for natural gas. Replace the fi replace. screws. 2.
  • Page 31: Replacements

    Contact your dealer for questions concerning prices and WARNING availability of replacement parts. Normally all parts can be ordered through your Napoleon® dealer or distributor. Failure to position the parts in accordance with these diagrams or When ordering replacement parts always give the following...
  • Page 32 W415-0612 / C / 01.25.08 NorthlineExpress.com http://www.northlineexpress.com Toll-Free 1-866-667-8454...
  • Page 33: Trouble Shooting Guide

    TROUBLE SHOOTING GUIDE EFORE ATTEMPTING TO TROUBLESHOOT PURGE YOUR UNIT AND INITIALLY LIGHT THE PILOT AND THE MAIN BURNER WITH THE GLASS DOOR REMOVED SYMPTOM PROBLEM TEST SOLUTION Pilot will not light. - Wiring Verify the "S" wire for the sensor and the "I" wire for the ignitor are Makes noise with no connected to the correct terminals (not reverse) on the module and spark at pilot burner...
  • Page 34 SYMPTOM PROBLEM TEST SOLUTION Inspect all wires, ensure good tight connections. Verify that all - Wiring / Connection Pilot lights wiring is installed exactly as specifi ed. Stops sparking / pilot remains lit Inspect the wiring harness, and verify the harness is tightly con- - Wiring harness but burner will nected to the module.
  • Page 35 W415-0612 / C / 01.25.08 NorthlineExpress.com http://www.northlineexpress.com Toll-Free 1-866-667-8454...
  • Page 36 NOTES W415-0612 / C / 01.25.08 NorthlineExpress.com http://www.northlineexpress.com Toll-Free 1-866-667-8454...