Product Information MAGIC.SENS -- Product range
5.2. Technical Data: O 400 E LSN / T 400 E LSN
Detector type
Detection principle
Special features
Operating voltage
Current consumption
Individual display
Alarm output
Indicator output
Response sensitivity
(basic data)
max. monitoring area
maximum mounting
height
permissible airspeed
permissible operation
temperature
Permissible relative
humidity
Protection category
according to
EN 60 529
Color code
Dimensions
Housing material
--/Color
Product ID
Table: Response sensitivity of the thermodifferential unit according to EN 54--5
Temperature
Response time for detectors in the
rate- -of- -rise
- - 1
1
[K
[K min
i
]
]
Lower limiting
value [min / sec]
10
20
30
O 400 E LSN
Scattered light measurement
Contamination detection
Drift compensation in optical unit
max. 15mA (in case of alarm 0 volts is put through)
< 0,15 dB/m (EN 54 T7)
2
120 m
(note VdS-guidelines)
16 m (note VdS-guidelines)
--20°C . . . +65°C
--
∅ 99.5 x 52mm (without base) / ∅ 120 x 63.5mm (with base)
ABS (Novodur) / white, similar to RAL 9010, matte surface
4.998.121.032
sensitivity class A1R
Upper limiting
value [min / sec]
1 min
4 min 20 sec
30 sec
2 min 20 sec
20 sec
1 min 40 sec
T 400 E LSN
Measurement of absolute temperature and
temperature increase
15 V DC . . . 33 V DC
< 0.7mA
LED red
per data word via two--wire signal line
Thermomaximum unit:> 54°C / > 69°C
Thermodifferential unit: according to EN 54 T5
(see table below)
20m/s
< 95 % (non--condensing)
IP 30
Response time for detectors in
sensitivity classes A2R / BR
Lower limiting value
[min / sec]
2 min
1 min
40 sec
Page 15 of 42
PI -- 34.65d
2
40 m
(note VdS-guidelines)
7,5 m (note VdS-guidelines)
--20°C . . . +50°C
or +65°C
red ring
4.998.130.603
Upper limiting value
[min / sec]
5 min 30 sec
3 min 13 sec
2 min 25 sec
BDL- -4998121218
A23.en /09.02.2007
ST- -FIR/ PRM1 / deh