5.3. Technical Data: OC 310 GLT / OT 300 GLT / O 300 GLT
Detector type
OC 310
Detection principle
Combination of:
--Scattered light measurement
--Gas measurement
Special features
Drift compensation in optical
unit and in gas measuring
unit
Operating voltage
Current consumption
Individual display
Alarm output
Indicator output
Response sensitivity
O unit: < 0.15 dB/m
(basic data)
(EN 54 T7)
Gas unit:in the ppm range
max. monitoring area
maximum mounting
height
permissible airspeed
Permissible operating
temperature
permissible relative
humidity
Protection category
according to
EN 60 529
Color code
Dimensions
Housing material
--/Color
Product ID
OT 300
Combination of:
--Scattered light measurement
--Measurement of absolute
temperature and temperature
increase
Current increase (alarm resistance approximately 800Ω)
Open collector, puts through 0 Volt via 3.92kΩ, max. 15mA
O unit: < 0.15 dB/m
(EN 54 T7)
T unit: EN 54--5
Thermomaximum unit: >54°C
Thermodifferential unit: see
table on page 15
120 m
--10°C . . . +50°C
--20°C . . . +50°C
blue ring
∅ 99.5 x 52mm (without base) / ∅ 120 x 63.5mm (with base)
ABS (Novodur) / white, similar to RAL 9010, matte surface
4.998.101.153
Page 16 of 42
Drift compensation in optical unit
12 V DC . . . 28 V DC
< 0.1mA
LED red
2
(note VdS-guidelines)
16 m (note VdS-guidelines)
20m/s
< 95 % (non--condensing)
IP 30
black ring
4.998.025.351
PI -- 34.65d
O 300
Scattered light measurement
O unit: < 0.15 dB/m
(EN 54 T7)
--20°C . . . +65°C
--
4.998.117.239
BDL- -4998121218
A23.en /09.02.2007
ST- -FIR/ PRM1 / deh