Product Information MAGIC.SENS -- Product range
5.4. Technical data: T 300 GLT / T 300 FSA GLT
Detector type
T 300
Detection principle
Measurement of absolute temperature and
temperature increase
Special features
Operating voltage
Current
consumption
Individual display
Alarm output
Indicator output
Response
T unit: EN 54--5
sensitivity
Thermomaximum unit: > 54°C
(basic data)
Thermodifferential unit: see table on page15
max. monitoring
area
maximum
mounting height
permissible
airspeed
Permissible
operating
temperature
permissible
relative humidity
Protection
category
according to
EN 60 529
Color code
Dimensions
Housing material
--/Color
Product ID
Class A2R according to EN 54--5
Current increase (alarm resistance approximately 800Ω)
Open collector, puts through 0 Volt via 3.92kΩ, max. 15mA
2
40m
(note VdS-guidelines)
6m (note VdS-guidelines)
--20°C . . . +50°C
red ring
∅ 99.5 x 52mm (without base) / ∅ 120 x 63.5mm (with base)
ABS (Novodur) / white, similar to RAL 9010, matte surface
4.998.025.354
Page 17 of 42
T 300 / FSA
Measurement of absolute temperature and
temperature increase
Goods monitoring for fire barriers
Characteristic curve according to class A1R
12 V DC . . . 28 V DC
< 0.1mA
LED red
T unit: EN 54--5
Thermomaximum unit: > 54°C
Thermodifferential unit: see table on page15
40m
6m (note VdS-guidelines)
20m/s
<95% (non--condensing)
IP 30
PI -- 34.65d
according to DIBt.
according to EN 54--5
2
(note VdS-guidelines)
--20°C . . . +50°C
red ring
4.998.107.056
BDL- -4998121218
A23.en /09.02.2007
ST- -FIR/ PRM1 / deh