Product Information MAGIC.SENS -- Product range
7.6.3. Connecting the MPA
The MPA external detector alarm display is connected using 4 Wago clamps.
Clamping on: insert isolated solid wire into the clamp.
Disconnecting: Turn wire alternately to the left and right ,
Up to 4 detectors can be connected to each MPA.
Three inputs (T. 2 – 4) allow adjustment to the various line networks. If used in
ex--area, only 2 inputs (T.3 and T. 4) can be used!
Connecting depending on the line technique used
Line
technique
GLT
GLT
LSN
Connection when using in explosive areas of the Zone 2
Line
technique
GLT
LSN
. Short- -circuit T. 1 and T. 2;
Terminal occupation
T.1: Ground
T.2: Input blinking (LED blinks),
T.3: Input static (LED lights up),
T.4: Input static (LED lights up)
On T.4 only connect via a current limiting resistor
(integrated in LSN detector); otherwise, the LED could be destroyed.
7.6.4. MPA Technical Data
Operating voltage
Cu e t co su pt o
Current consumption for display
Weight
Display medium
Permissible wire diameter
VdS ID number
thus pulling it out of the terminal.
Fire panels
BZ 1060
UEZ 1000, UGM 2020, FP 102, 104, 106
BZ 500, UEZ 1000, UEZ 2000, UGM 2020 T.1 + T.4
Fire panels
UGM 2020, FP 102, FP 104, FP 106
BZ 500, UEZ 1000, UEZ 2000, UGM 2020 T.1 + T.4
limit T. 4 to maximum of 20mA!
o d sp ay
Page 28 of 42
9 V DC . . . 30 V DC
T.2
approx. 2 mA
T.3
limited to approx. 13 mA
T.4
limited to approx. 20 mA
65 g
1 LED via a light conductor
0.6 mm --0.8 mm
G 294 052
PI -- 34.65d
Terminals
T.1 + T.2
T.1 + T.3
Terminals
T.1 + T.3
1 2 3 4
BDL- -4998121218
A23.en /09.02.2007
ST- -FIR/ PRM1 / deh