Product Information MAGIC.SENS -- Product range
11.2. Test Instructions for MAGIC.SENS Fire Detectors
The newest generation of MAGIC.SENS OTC 410 LSN/ OC 410 LSN and OC 310 GLT
multisensor fire detectors have an additional sensor for CO detection in case of fire.
The CO sensor causes improved response behavior and increased malfunction
suppression in critical environmental conditions.
For fire recognition, MAGIC.SENS detectors use the time behavior of the fire variables
that deviates significantly from the time behavior of disturbance variables and also
from the time behavior of a detector check with aerosol.
Therefore, for a functional test, the detector must be switched into maintenance mode.
Switching into maintenance mode occurs differently for LSN and GLT detectors.
11.3. Inspection procedure for MAGIC.SENS OTC 410 LSN /
OC 410 LSN
D Switch the detector zone to be inspected into maintenance mode on the central
unit. Thus the detector is set automatically into maintenance operation and
prepared for the detector test.
. Only in maintenance operation can the detector's individual sensors be made to
trigger one after the other with the corresponding test device. For this, you should
use the service accessories we recommend.
D The optical sensor is tested with the detector tester for smoke detectors with the
Solo A3--001 testing gas.
NOTE:
D To test the CO -- sensor, the same test device is used, but exchange the testing
gas bottle Solo A3--001 for the CO testing gas bottle. For the CO -- test, a testing
gas application of
NOTE:
D The temperature sensor of the OTC is tested with the test device for heat detectors.
11.4. Test procedure for MAGIC.SENS OT 400 E LSN /
O 400 E LSN
D Switch the detector zone to be inspected into maintenance mode on the central
unit. Thus the detector is set automatically into maintenance operation and
prepared for the detector test.
. Only in maintenance operation can the detector's individual sensors be made to
trigger one after the other with the corresponding test device. For this, you should
use the service accessories we recommend.
D The optical sensor is tested with the detector tester for smoke detectors with the
Solo A3--001 testing gas.
NOTE:
D The temperature sensor of the OT is tested with the test device for heat detectors.
The transceiver must remain over the detector until the detector has been
triggered. The distribution of the test aerosol in the transceiver and thus the
triggering time of the sensor can take up to 10 seconds.
1
/
to 1 seconds in duration must be made.
2
The transceiver must remain over the detector until the detector has been
triggered. The distribution of the CO gas in the transceiver and thus the
triggering time of the sensor can take up to 20 seconds.
The transceiver must remain over the detector until the detector has been
triggered. The distribution of the test aerosol in the transceiver and thus the
triggering time of the sensor can take up to 10 seconds.