Product Information MAGIC.SENS -- Product range
3.4. Use in Explosive Areas
All MAGIC.SENS detector types conform to the device category 3G,
gas group IIB, and temperature class T6, in accordance with the
European guideline 94/9/EG (ATEX). Thus the detectors may be
used in Zone 2 areas where there is danger of explosion!
Limiting values:
D Detectors may only be operated with central units whose line output is
energy- -limited according to EN 50021.
. This is a given for all Bosch fire panels.
D The line voltage (U
D The maximum current (I
D The auxiliary voltage may not be fed through the ex area!
Fire detector cable:
D Only fire detector cables that conform to DIN VDE 0814 may be used.
D The entire cable capacity (C
D The entire cable inductivity (L
. The cable type J--Y(ST)Y08, according to DIN VDE 0815 (Table 10),
has a capacity of 120ηF with a length of 1000m.
Detector heating element:
The use of a detector heating element (MH 400) is not permissible!
D
3.5. Use in Areas with Elevated Radioactivity
D There are three LSN detector types available especially for use in areas with
elevated radioactivity, such as in nuclear power plants:
-- Magic.Sens OT 400 LSN KKW
-- Magic.Sens O 400 LSN KKW
-- Magic.Sens T 400 LSN KKW
3.6. Use in Fire Barriers according to DIBt
D There are four detector types available for use in fire barriers according to the
guideline of the DIBt (German Institute for Building Technology):
-- Magic.Sens O 400 LSN KKW
-- Magic.Sens T 400 LSN KKW
-- Magic.Sens O 300 GLT
-- Magic.Sens T 300 / FSA GLT
) may not exceed 33V!
max
) must be limited to 130mA!
max
) may not exceed 1mF!
max
) may not exceed 0.01H!
max