80070301-0302ffff • 80070608-0a01ffff
User response:
1.
Make sure that the fans are operating, that there
are no obstructions to the airflow (front and rear of
the server), that the air baffle is in place and
correctly installed, and that the server cover is
installed and completely closed.
2.
Check the ambient temperature. You must be
operating within the specifications (see Server
Features and specifications for more information).
3.
Make sure that the heat sink for microprocessor n.
4.
(Trained technician only) Replace microprocessor n.
(n = microprocessor number)
80070301-0302ffff
Sensor [SensorElementName] has
transitioned to non-recoverable from a
less severe state. (CPU 2 OverTemp)
Explanation: This message is for the use case when an
implementation has detected a Sensor transitioned to
non-recoverable from less severe.
May also be shown as 800703010302ffff or
0x800703010302ffff
Severity: Error
Alert Category: Critical - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0524
SNMP Trap ID: 0
Automatically notify Support: No
User response:
1.
Make sure that the fans are operating, that there
are no obstructions to the airflow (front and rear of
the server), that the air baffle is in place and
correctly installed, and that the server cover is
installed and completely closed.
2.
Check the ambient temperature. You must be
operating within the specifications (see Server
Features and specifications for more information).
3.
Make sure that the heat sink for microprocessor n.
4.
(Trained technician only) Replace microprocessor n.
(n = microprocessor number)
80070603-0701ffff
Sensor [SensorElementName] has
transitioned to non-recoverable. (Pwr
Rail 1-6 Fault)
Explanation: This message is for the use case when an
implementation has detected a Sensor transitioned to
non-recoverable.
May also be shown as 800706030701ffff or
0x800706030701ffff
Severity: Error
Alert Category: Critical - Power
370
System x3550 M4 Type 7914: Installation and Service Guide
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0530
SNMP Trap ID: 4
Automatically notify Support: No
User response: If the specified sensor is one of Pwr
Rail 1-6 Fault, please follow actions in "Power Problems
and Solving Power Problems".
80070608-0a01ffff
Sensor [SensorElementName] has
transitioned to non-recoverable.
Explanation: This message is for the use case when an
implementation has detected a Sensor transitioned to
non-recoverable.
May also be shown as 800706080a01ffff or
0x800706080a01ffff
Severity: Error
Alert Category: Critical - Power
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0530
SNMP Trap ID: 4
Automatically notify Support: No
User response: If the specified sensor is PS n 12V OC
Fault, complete the following steps until the problem is
solved:
1.
Use the IBM Power Configurator utility to
determine current system power consumption. For
more information and to download the utility, go to
http://www-03.ibm.com/systems/bladecenter/
resources/powerconfig.html.
2.
Follow actions in "Power Problems and Solving
Power Problems".
If the specified sensor is PS n 12V OV Fault, complete
the following steps until the problem is solved:
Check power supply n LED.
1.
2.
Remove the failing power supply.
3.
(Trained technician only) Replace the system board.
(n = power supply number)
If the specified sensor is PS n 12V UV Fault, complete
the following steps until the problem is solved:
1.
Check power supply n LED.
Remove the failing power supply.
2.
Follow actions in "Power Problems and Solving
3.
Power Problems".
(Trained technician only) Replace the system board.
4.
(n = power supply number)
If the specified sensor is PS n 12Vaux Fault, complete
the following steps until the problem is solved: