1
Reference diagram for snow-proof vents – 2
Space requirements for setting – (2)
The models of SPW-C256 / 366VH8 with STK-BDRE80A
[Obstacle to the front and rear of unit]
The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must
be no taller than the height of the outdoor unit.
(1) Single-unit installation
(2) Obstacles on both sides
Min. 300
[Installation in front-rear rows]
The top and both sides must remain open. Either the obstacle to the front or the obstacle to the
rear must be no taller than the height of the outdoor unit.
Min. 1000
Dimension Q
If a snow protection duct is attached after the unit is
installed, verify that dimension Q is 500 mm or more.
Outdoor unit
SPW-C256 / 366VH8
Min. 300
Min. 300
Min. 1500
O
P
1000 150
0
Min. 2000
1-348
Min. 200
Dimension Q
If a snow protection duct
is attached after the unit is
installed, verify that dimension
Q is 500 mm or more.