(Wiring procedure)
(1) Connect the remote controller to the indoor unit remote controller wiring terminal plate (1, 2).
(Remote controller wiring)
(2) Connect the indoor units (U1, U2) and the outdoor units (1, 2). Connect the other outdoor units and indoor units
(with different refrigerant systems) in the same way. (Inter-unit control wiring)
Connect the remote controller communication wiring to the indoor units (U1, U2) for each refrigerant system.
(Interunit control wiring)
(3) Connect the remote controller communication wiring (2 wires) from the remote controller wiring terminal plate (1,
2) on the indoor unit (unit where the remote controller is connected) to the remote controller terminal plates (1,
2) on the other indoor units. (Remote controller communication wiring)
(4) Turn ON both the indoor and outdoor unit power and perform automatic address setting from the remote
controller. (For the automatic address setting procedure, refer to 2-8-4.)
NOTE
* Models with auxiliary heaters cannot be used for crossover wiring of the indoor unit power wires.
(Use a pull box to divide the wiring.)
Be sure to use the indoor unit temperature sensor (body sensor) when using this control. (Status at shipment.)
2-8-3. Setting the outdoor unit system addresses
For basic wiring diagram 2 (Set the system addresses: 1, 2, 3...)
Outdoor unit control PCB
System address rotary switch (Set to "0" at time of shipment)
System address rotary switch
System address
DIP switch
10s
20s
ON
ON
1
2
OFF
SPW-C256/366VH
HIC
Temperature
sensor
Up side
C2 (CN020, WHT)
MOV (CN25, WHT)
Bottom
side
SPW-C486VH
F101
MOV
(CN025, WHT)
TD (CN024, BLK)
TO (CN023, BLK)
TS (CN022, RED)
System address
System
10s digit
address No.
(2P DIP switch)
Both OFF
ON
0
ON
Automatic address
(Setting at shipment = "0")
1
2
OFF
Both OFF
ON
1
(If outdoor unit is No. 1)
1
2
OFF
Both OFF
ON
ON
2
(If outdoor unit is No. 2)
1
2
OFF
AUTO ADD (CN041)
System address
Rotary switch (S002)
TERMINAL (S010)
JP007
System address
DIP switch (S003)
RC-P (CN032,RED)
LED1
LED2
PUMP DOWN (CN042)
EEPROM (IC006)
C1 (CN021, BLK)
TO (CN022, WHT)
TD, TS (CN023, WHT)
EXCT (CN026, RED)
SILENT (CN028, WHT)
RC-P (CN032, RED)
FAN (CN030, WHT)
ROM (CN012, WHT)
OC (CN013, BLU)
EMG (CN014, BRN)
20S (CN09, WHT)
FUSE (25A, F003)
Varistor (VA002)
JP007
Varistor (VA001)
Terminal plug (CN015, BLK)
EMG (CN014, BRN)
OC (CN013, BLU)
ROM (CN012, WHT)
EEPROM (IC007)
PRY (CN110, YEL)
C2 (CN020, WHT)
C1 (CN021, WHT)
System address
System
1s place
address No.
(Rotary switch)
"0" setting
11
(If outdoor unit is No. 11)
"1" setting
ON
21
(If outdoor unit is No. 21)
"2" setting
30
(If outdoor unit is No. 30)
SPW-C256/366VH8
SPW-C486/606VH8
2-7
System address
System address
10s digit
1s place
(2P DIP switch)
(Rotary switch)
10s digit ON
"1" setting
ON
ON
1
2
OFF
20s digit ON
"1" setting
ON
ON
1
2
OFF
10s digit and 20s
"0" setting
digit ON
ON
ON
1
2
OFF
System address rotary switch
System address 10s digit and 20s digit
DIP switch
Automatic address
button (black)
Terminal plug (black)
Terminal plug (CN015, BLK)
OC (CN013, BLU)
EMG (CN014, BRN)
JP007
ROM (CN012, WHT)
EEPROM (IC007)
TD (CN024, BLK)
TO (CN023, BLK)
MOV(CN025, WHT)
C2 (CN020, WHT)
C1 (CN021, WHT)
TS (CN022, RED)
Fig. 2-7
2