2-16-3. Setting the outdoor unit system addresses
For basic wiring diagram 2 (Set the system addresses: 1, 2,...)
Outdoor unit control PCB
System address rotary switch
(Set to "0" at time of shipment)
System address rotary switch
System address
DIP switch
10s
20s
ON
ON
OFF
1
2
SPW-C256/366VH
HIC
Temperature
sensor
Up side
C2 (CN020, WHT)
MOV (CN25, WHT)
Bottom
side
SPW-C486VH
F101
MOV
(CN025, WHT)
TD (CN024, BLK)
TO (CN023, BLK)
TS (CN022, RED)
2-16-4. Automatic address setting from the outdoor unit
When there are multiple outdoor units as shown in basic wiring diagram 2
• If the power can be turned ON separately for the indoor and outdoor units in each system
(indoor unit addresses can be set without operating the compressor):
(1) Turn ON the indoor and outdoor unit power for refrigerant system 1.
Press and hold the automatic address setting button (black) for 1 second or longer at the outdoor unit where the
power was turned ON.
Communication for automatic address setting begins. LED 1 and 2 on the outdoor unit control PCB blink
alternately, and turn OFF when address setting is completed.
(2) Next, turn ON the power only at the indoor and outdoor units in a different system. Press the automatic address
setting button (black) on the outdoor unit.
LED 1 and 2 on the outdoor unit control PCB blink alternately, and turn OFF when address setting is completed.
Repeat the same procedure for each system and complete automatic address setting.
(3) Operation using the remote controller is now possible.
2-16-5. Indoor unit remote controller main-sub setting
• When multiple wall-mounted indoor units are installed for group control in a simultaneous operation multi system,
set the control PCB at the No. 2 and following wall-mounted units to "Sub remote control".
If a wired remote controller is used, set the wired remote controller to "Sub".
If 2 wireless remote controllers are used, set the wireless PCB (DIP switch) on the second remote controller to "Sub".
System address
System
10s digit
address No.
(2P DIP switch)
Both OFF
0
ON
ON
Automatic address
(Setting at shipment = "0")
1
2
OFF
Both OFF
1
ON
ON
(If outdoor unit is No. 1)
1
2
OFF
Both OFF
ON
2
ON
(If outdoor unit is No. 2)
1
2
OFF
AUTO ADD (CN041)
System address
Rotary switch (S002)
TERMINAL (S010)
JP007
System address
DIP switch (S003)
RC-P (CN032,RED)
LED1
LED2
PUMP DOWN (CN042)
EEPROM (IC006)
C1 (CN021, BLK)
TO (CN022, WHT)
TD, TS (CN023, WHT)
EXCT (CN026, RED)
SILENT (CN028, WHT)
RC-P (CN032, RED)
FAN (CN030, WHT)
ROM (CN012, WHT)
OC (CN013, BLU)
EMG (CN014, BRN)
20S (CN09, WHT)
FUSE (25A, F003)
Varistor (VA002)
JP007
Varistor (VA001)
Terminal plug (CN015, BLK)
EMG (CN014, BRN)
OC (CN013, BLU)
ROM (CN012, WHT)
EEPROM (IC007)
PRY (CN110, YEL)
C2 (CN020, WHT)
C1 (CN021, WHT)
<Approximately 4 – 5 minutes are required.>
System address
System
1s place
address No.
(Rotary switch)
"0" setting
11
(If outdoor unit is No. 11)
"1" setting
21
(If outdoor unit is No. 21)
"2" setting
30
(If outdoor unit is No. 30)
SPW-C256/366VH8
System address rotary switch
SPW-C486/606VH8
2-15
System address
System address
10s digit
1s place
(2P DIP switch)
(Rotary switch)
10s digit ON
"1" setting
ON
ON
1
2
OFF
20s digit ON
"1" setting
ON
ON
1
2
OFF
10s digit and 20s
digit ON
"0" setting
ON
ON
1
2
OFF
System address 10s digit and 20s digit
DIP switch
Automatic address
button (black)
Terminal plug (black)
Terminal plug (CN015, BLK)
OC (CN013, BLU)
EMG (CN014, BRN)
JP007
ROM (CN012, WHT)
EEPROM (IC007)
TD (CN024, BLK)
TO (CN023, BLK)
MOV(CN025, WHT)
C2 (CN020, WHT)
C1 (CN021, WHT)
TS (CN022, RED)
Fig. 2-13
2