free hit counter

Processor Board Leds; Serveraid; Undetermined Problems - IBM xSeries 200 Hardware Maintenance Manual

Hide thumbs Also See for xSeries 200:
Table of Contents

Advertisement

Processor board LEDs

Table 16.
LED
Fan
Memory
CPU
VRM

ServeRAID

For ServeRAID error codes and procedures, refer to the
Hardware Maintenance Manual for the particular RAID
adapter in the system being serviced.

Undetermined problems

You are here because the diagnostic tests did not identify
the failure, the Devices List is incorrect, or the system is
inoperative.
Note: A corrupt CMOS can cause undetermined problems.
If power problems are suspected:
1. Power-off the computer.
2. Be sure the system is cabled correctly.
3. Remove or disconnect the following (one at a time)
until you find the failure (power-on the computer and
reconfigure each time).
v Any external devices
v Surge suppressor device (on the computer)
v Modem, printer, mouse, or non-IBM devices
v Each adapter
v Drives
116
Hardware Maintenance Manual: xSeries 200
Cause
1. Replace the fan assembly.
1. Replace the DIMM indicated by the lit DIMM
error.
1. If a microprocessor LED is on for a
microprocessor connector that has a terminator
card installed instead of a microprocessor, the
microprocessors are not installed in the correct
order. See "Removing and installing a
microprocessor" on page 63 for information
about the correct order for installing
microprocessors and VRMs.
2. Turn off the server, reseat the microprocessor,
and restart the server.
3. Replace the microprocessor.
1. Turn off the server, reseat the VRM indicated
by the lit VRM error LED, and restart the
server.
2. Replace the VRM

Advertisement

Table of Contents
loading