16
en | Connecting cables in housing
6.4
Power connections
Caution!
To protect the device, the branch circuit protection must be secured with a maximum fuse
!
rating of 16A. This must be in accordance with NEC 800 (CEC Section 60).
Caution!
!
The external ground wire must always be connected to the main ground post inside the
housing.
6.4.1
Incoming power safety earth connection
Connect the incoming power safety earth wire to the grounding post on the PCB bracket
assembly as follows:
1.
2.
3.
4.
1
2
3
4
5
2014.11 | 1.0 | F.01U.309.609
A terminal lug (4) is provided for connecting the incoming power safety earth wire.
Remove the nut, the washers, and the ground wire lug from the grounding post (5).
Strip the incoming power safety earth wire and crimp into the lug.
Reattach the ground connections in the order shown:
Nut
Lock washer
Flat washer
Input power ground lug
Grounding post
Installation Manual
DINION Housing Kit
Bosch Security Systems