F
MULTI
F
MULTI
MAX
Model Name
Nominal Cooling Capacity (Btu/h)
Nominal Heating Capacity (Btu/h)
Operating Range
Cooling (°F WB)
Heating (°F DB)
Fan
Type
Motor Output (W) x Qty.
Motor/Drive
Airflow Rate CFM (H/M/L)
Unit Data
Refrigerant Type
2
Refrigerant Control
Power Supply V, Ø, Hz
3
Rated Amps (A)
Sound Pressure Level ±3 dB(A) (H/M/L)
Dimensions (W x H x D, in.)
Net Unit Weight (lbs.)
Shipping Weight (lbs.)
Power Wiring / Communications Cable (No. x AWG)
Heat Exchanger (Row x Column x Fin / inch) x No.
Pipe Size
Liquid (in.)
Vapor (in.)
Connection Size
Liquid (in.)
Vapor (in.)
Drain O.D. / I.D. (in.)
Nominal capacity is rated 0 ft. above sea level with corresponding refrigerant piping
1
length in accordance with standard length of each outdoor unit and a 0 ft. level difference
between outdoor and indoor units. All capacities are net with a combination ratio between
95 – 105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb
(DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and
75ºF wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb
(DB) and 60ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and
43ºF wet bulb (WB).
Table 4: Multi F Multi Zone Art Cool Mirror Wall-Mounted Indoor Unit Specifications
1
1
4
34-13/16 x 11-1/4 x 8-1/16
5
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
LAN090HSV4
LAN120HSV4
9,000
10,400
14.4 x 1
Brushless Digitally Controlled / Direct
247 / 230 / 212
335 / 318 / 300
Electronic Expansion Valve (EEV)
208-230, 1, 60
0.2
33 / 30 / 27
34-13/16 x 11-1/4 x 8-1/16
24
29
(2 x 16 x 23) x 1
3/8
1/4
3/8
This unit comes with a dry helium charge.
2
Acceptable operating voltage: 187V-253V.
3
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and
4
are the same in both cooling and heating mode. These values can increase due to ambient
conditions during operation.
All power wiring / communications cable to be minimum 18 AWG, 4-conductor, stranded,
5
shielded, and must comply with applicable local and national codes.
GENERAL DATA
Specifications
LAN180HSV4
12,000
13,800
57-77
59-81
Cross Flow
572 / 501 / 434
R410A
39 / 36 / 31
37 / 33 / 28
40-9/16 x 12-13/16 x 9-11/16
4 x 18
(3 x 18 x 22) x 1
1/4
27/32, 5/8
18,000
20,800
76.0 x 1
0.3
32
39
1/2
3/8
5/8
13