Cycle Settings Validation Settings Parameter Server Upload Flag on the IO-Link Device Configuration via Explicit Messages QuickConnect Rockwell Automation Products that are Compatible with QuickConnect Example with Rockwell Components PLC Program Fault State Enable/Disable Fault State Fault State Action www.balluff.com...
Page 3
Balluff Network Interface EtherNet/IP™, BNI EIP-50x-105-R015 IO-Link Device Parameterization Read IO-Link Parameter Write IO-Link Parameter Process Data 7.1. Process Data Inputs Standard Input Data IO-Link Input Data 7.2. Process Data Outputs Standard Output Data IO-Link Output Data Display 8.1. General 8.2.
Cross-references indicate where additional information on the topic is located. 1.4. Symbols This symbol indicates general notes. Note This symbol indicates a security notice which most be observed. 1.5. Abbreviations Balluff Network Interface Standard input port EtherNet/IP™ Electromagnetic compatibility Function ground Standard output port...
Before working on the device, switch off its power supply. Note In the interest of continuous improvement of the product, Balluff GmbH reserves the right to change the technical data of the product and the content of these instructions at any time without notice. www.balluff.com...
First Steps 3.1. Module Overview Figure – Overview: BNI EIP-508-105-R015 Mounting hole Port 7 (IO-Link, standard I/O) EtherNet/IP™ port 2 Port 3 (IO-Link, standard I/O) Display Port 2 (IO-Link, standard I/O) Power supply, input Port 1 (IO-Link, standard I/O) Status LED: communication / module...
Balluff Network Interface EtherNet/IP™, BNI EIP-50x-105-R015 First Steps 3.2. Mechanical Con- The module is secured by means of two M6 screws and two washers. nection Insulation support is available separately. 3.3. Electrical Con- nection Power Supply Function Description +24 V...
Unused I/O ports must be provided with cover caps to comply with degree of protection IP67. IO-Link Port M12, A-coded, female Function +24 V, 1.6 A Input/output 2 A IO-Link/input/output 2 A n.a. Port Port BNI EIP-502-105-R015 IN / OUT IN / OUT / IO-Link BNI EIP-508-105-R015 IN / OUT / IO-Link www.balluff.com...
Module has no IP address Green, flashing Module has IP, but no connection established Net- Green Connection established work Red, flashing Connection timeout Red-green, flashing Initial sequence Bus clock: 10 Mbps Yellow Bus clock: 100 Mbps Green Data transfer www.balluff.com...
Balluff Network Interface EtherNet/IP™, BNI EIP-50x-105-R015 Technical Data Port Each port has two bicolored LEDs for displaying the I/O statuses. Display Status Description I/O status The status of the input or output pins is 0 Yellow I/O status The status of the input or output pins is 1...
Integration Here you see an example of how the module can be integrated into a Rockwell RS Logix 5000: First go offline Right-click Ethernet (on the correct scanner card) Select a new module www.balluff.com...
Page 13
Balluff Network Interface EtherNet/IP™, BNI EIP-50x-105-R015 Integration Then select the general Ethernet module as the ETHERNET module in the communication path Now enter a user-defined tag name to select the general format Data-SINT, to enter the IP address of the module and to enter the correct connection parameters.
Page 14
Integration The new module and corresponding controller tags are generated automatically. Then download the configuration www.balluff.com...
Page 15
Balluff Network Interface EtherNet/IP™, BNI EIP-50x-105-R015 Integration When the download is done, you can observe and control the tags using the Controller Tags option. Make sure you select the correct tag name, which you configured beforehand. The input, output and configuration data for this is described on the following pages.
BNI EIP-502-105-R015 Instance ID Data length INPUT OUTPUT CONFIG BNI EIP-508-105-R015 Instance ID Data length INPUT OUTPUT CONFIG 5.2. Configuration The following tables show an allocation of the configuration data sequence. The standard Data values specified below describe a configuration with the IO-Link function at Pin 4 and stand- ard I/O functions at Pin 2 and 4 of each port.
Balluff Network Interface EtherNet/IP™, BNI EIP-50x-105-R015 Integration IO-Link Port Con- BNI EIP-502-105-R015 and BNI EIP-508-105-R015 figuration Description Basic Time Cycle time Validation type 0 No validation Validation type 1 compatible (VID + DID) 2 Identical (VID + DID + SerNum)
If the upload flag is set on the IO-Link device, an upload of the parameter data always takes place. If no upload flag is set and parameter data has already been stored, a download of the parameter data always takes place. www.balluff.com...
Balluff Network Interface EtherNet/IP™, BNI EIP-50x-105-R015 Integration Note After the upload of the parameter data, the vendor ID and device ID of the con- nected IO-Link device are also still saved until the data records are deleted. When the connected IO-Link device is started, a validation takes place. Thus, only an IO-Link device of the same type can be used for the data management.
If needed, only one managed switch may be used between the PLC and Ethernet/IP slave. To trigger the QuickConnect sequence, an electrical lock signal is required that reads in the supply voltage of the QuickConnect slaves via the controller. www.balluff.com...
The fault state settings are stored only temporarily in the module. They are deleted after a power reset. To ensure a long-term fault state configuration, the configuration has to be pro- grammed via the PLC so that the settings are transferred to the module again when the system is restarted. www.balluff.com...
Balluff Network Interface EtherNet/IP™, BNI EIP-50x-105-R015 Configuration via Explicit Messages IO-Link Device There are two options for configuring an IO-Link device connected to the IO-Link port. Parameteriza- tion Configuration via the web server refer to the "Web Server" chapter under "Device Properties"...
Page 28
Destination Array (Read) shows the read-out value. In case of a configuration error, the error code is likewise displayed there. In the "Communication" window, you have to select the Ethernet module on which the configuration is to take place. www.balluff.com...
IO-Link port 6 Process data inputs at IO-Link port 6 344…391 IO-Link port 7 Process data inputs at IO-Link port 7 Standard Input BNI EIP-502-105-R015 and BNI EIP-508-105-R015 Data Description Input data Input at port 0, pin 4 The result is 0 only if the port is configured as an IO-Link port.
Balluff Network Interface EtherNet/IP™, BNI EIP-50x-105-R015 Process Data IO-Link Input Data BNI EIP-502-105-R015 and BNI EIP-508-105-R015 Description … IO-Link port 0 input data IO-Link status IOL: Port in IO-Link mode DC: Device connected 0: Reserved IO-Link error VF: Validation failed...
IO-Link port 6 Process data output at IO-Link port 6 230…261 IO-Link port 7 Process data output at IO-Link port 7 Standard Output BNI EIP-502-105-R015 and BNI EIP-508-105-R015 Data Byte Description Output data Output at port 0, pin 4...
Balluff Network Interface EtherNet/IP™, BNI EIP-50x-105-R015 Display With the implemented display, the address is output directly to the devices BNI EIP… 8.1. General The following address types are possible: • IP address • Subnet mask • Gateway address Each address is composed of 4 octets.
Condition: Briefly press the Set key Condition: Press and hold the Set key (at least 3 seconds) Condition: Briefly press the arrow key 8.6. Startup B A L L U F F BALLUFF Module name EIP-508- 105-R015 VERSION Hardware and firmware update H W : 1 .
Balluff Network Interface EtherNet/IP™, BNI EIP-50x-105-R015 Display 8.8. IP Setup X STATIC IP editing mode DHCP FACTORY SETTI N G STATIC STATIC X STATIC DHCP X DHCP DHCP FACTORY SETTING X FACTORY SETTING FACTORY SETTING Editing mode •...
The plc lock function can also be used by setting a bit in the process data outputs. (see bit layout, standard output data) Note: You cannot select editing mode in the display if the plc lock is set in the process data inputs by a bit (see bit layout, standard output data) www.balluff.com...
For connection setup with the web server, enter the IP address of the module in the address line of the browser. A welcome page appears with a list of Balluff Ethernet network interfac- Please use Internet Explorer 7 or higher.
You can also see here whether the display lock was set via the control unit. The navigation bar appears in the upper area of the window, which allows you to switch between the various web pages. A click on the corresponding text is all it takes. www.balluff.com...
Balluff Network Interface EtherNet/IP™, BNI EIP-50x-105-R015 Web Server 9.3. Diagnostic Pro- On this page you can read some information about the current process data of the module cess and the status shown by the corresponding LEDs. If an IO-Link device is connected to one of the configured IO-Link terminals, some of the device data will be displayed in addition to the module data.
You can monitor only the process data of the connected IO-Link device, but cannot set the output data. If the IO-Link device requires output data, you have to set it via the control unit us- ing the corresponding software. www.balluff.com...
Page 41
Balluff Network Interface EtherNet/IP™, BNI EIP-50x-105-R015 Web Server This figure shows you the "Parameter Data" options for the IO-Link device. In addition, it is possible to read and configure the parameters of the IO-Link device via the "Parameter Data" option.
Web Server 9.5. Diagnostic Mod- The current status of the module and network appears on this page as shown on the mod- ule. The status is also discussed under "Description". www.balluff.com...
Balluff Network Interface EtherNet/IP™, BNI EIP-50x-105-R015 Web Server 9.6. Configurations The configuration page permits configuration of the module. You can change the addresses set under DHCP Client and add your own module information texts as well as a description of the module.