DUCT (LOW STATIC) INDOOR UNITS

Installation and Best Layout Practices

Selecting the Best Location
Do's
• Place the unit where air circulation will not be blocked.
• Place the unit where drainage can be obtained easily.
• Place the unit where noise prevention is taken into consideration.
• Ensure there is sufficient strength to bear the load of the indoor unit.
• Ensure there is sufficient maintenance space.
• Locate the indoor unit in a location that is level, and where it can be easily connected
to the outdoor unit / branch distribution unit.
Don'ts
• The unit should not be installed near a heat or steam source, or where considerable
amounts of oil, iron powder, or flour are used.
• The unit should not be installed where sulfuric acid and flammable or corrosive gases
are generated, vented into, or stored.
• Avoid installing the unit near high-frequency generators or near any equipment that gen-
erates an electromagnetic field (minimum 3-1/3 feet away).
• Do not install the unit near a doorway.
The unit may be damaged, may malfunction, and / or will not operate as
designed if installed in any of the conditions listed.
Installing in an Area Exposed to Unconditioned Air
In some installation applications, areas(floors, walls) in some rooms may be ex-
posed to unconditioned air (room may be above or next to an unheated garage
or storeroom). To countermeasure:
• Verify that carpet is or will be installed (carpet may increase the temperature
by three degrees).
• Add insulation between the floor joists.
• Install radiant heat or another type of heating system to the floor.
Installing in an Area with High Humidity Levels
If the environment is prone to humidity levels of 80% or more (near the ocean,
lakes, etc.) or where steam could collect in the plenum:
• Install additional insulation to the indoor unit (glass wool insulation >13/32
inches thick).
• Install additional insulation to the refrigerant piping (insulation >13/16 inches
thick).
• Seal all gaps between the indoor
tight) so that humidity does not transfer from the plenum to the conditioned
space. Also, add a ceiling grille for ventilation.
If the unit is installed near a body of water, certain components are at risk of being
corroded. Appropriate anti-corrosion methods should be taken for the unit and all
components.
102 | DUCT (LOW STATIC)
unit and the ceiling tiles (make the area air
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Figure 129:General Installation Guidelines.
Top view
Control box
23-5/8
Access Opening
23-5/8
(
x
Side view
H = ≤25/32
• "H" dimension is necessary to ensure a slope is included for
condensate drainage.
Figure 130:Service / Access Panel Dimensions.
B (Min)
A (Min)
Service Space
Table 52:General Access Panel Dimensions.
Model / Capacity (Btu/h)
LMDN096HV / 9,000
LMDN126HV / 12,000
LMDN186HV / 18,000
F
MULTI
F
MULTI
MAX
(Unit : Inch)
23-5/8
23-5/8
)
(Unit : Inch)
Ceiling
A
B
Dimensions (in.)
A
B
31-1/2
31-1/2
39-3/8