32 | Installation
6.2
Comparing the size of the integrated expansion
vessel (KWB-3A boiler only)
The following diagrams allow verifying that the integrated expansion
vessel has sufficient capacity for the intended application, or if an
additional expansion vessel is needed (not for radiant floor heating).
The following standard conditions were used:
• Pre-charge volume 20% of the rated volume in the expansion vessel
• Differential to the safety valve of 7.25 psi (0.5 bar)
• Pre-charge pressure of the expansion vessel equal to the static
system height above the boiler
• Maximum operating pressure: 30 psi (2.07 bar)
200
I
180
160
140
120
III
100
II
A
80
0
20
40
Fig. 16 Operating capacity of the expansion vessel in °F and gallons
90
I
80
70
60
50
III
40
II
A
30
0
75
150
Fig. 17 Operating capacity of the expansion vessel in °C and liters
Key to Fig. 16 and Fig. 17:
[I]
Pre-charge pressure 7.25 psi (0.5 bar) (default setting)
[II]
Pre-charge pressure 10.9 psi (0.75 bar)
[III]
Pre-charge pressure 14.5 psi (1.0 bar)
t
Supply temperature in °F ( °C)
V
V
System capacity in gallons (liters)
A
A
Within operating capacity of the expansion vessel (left of the
relevant curve)
B
Additional expansion vessel required (right of the relevant curve)
▶ If results are borderline: Determine precise vessel sizes.
▶ If the results are to the right of the curve: Install additional expansion
vessel.
6 720 810 590 (2015/05)
B
60
80
100
120
V
/gal
A
6720641933-13.1O
B
225
300
375
450
V
/l
A
6720641933-27.1O
6.3
KBR..-3A appliances (heating boilers): Selecting an

expansion vessel

External expansion vessel
▶ Determine size of the expansion vessel.
Fig. 18 Sample installation - expansion vessel
6.4

Selecting the installation location

Installation location requirements
Observe the current national and local codes and regulations.
▶ Observe country-specific requirements.
▶ Observe installation instructions of the venting system accessories
and their clearances.
Combustion air
To avoid corrosion, keep the supply of combustion air free of corrosive
substances; contained in solvents, paints, adhesives, propellants and
domestic cleaning agents.
Industrial sources
Chemical cleaning
Trichloroethylene, tetrachloroethylene,
fluorinated hydrocarbons
Degreasing bath
Perchloroethylene, trichloroethylene,
methylchloroform
Printing shops
Trichloroethylene
Hair salons
Aerosol propellants, hydrocarbons containing
fluorine and chlorine
(difluorodichloromethane)
Household sources
Cleaning and
Perchloroethylene, methylchloroform,
degreasing agents
trichloroethylene, methylene chloride, carbon
tetrachloride, hydrochloric acid
Workshop
Solvents and thinners Various chlorinated hydrocarbons
Aerosols
Chlorofluorinated hydrocarbons
(difluorodichloromethane)
Table 7 Corrosive materials
Surface temperature
The max. surface temperature of this appliance is below 185 °F (85 °C).
According to ANSI/Z223.1/NFPA43 (National fuel gas code) and CAN/
CGA B 149.1 (Natural Gas and Propane installation code), the appliance
is approved for zero clearance to combustibles. For servicing a
clearance of 4" (102 mm) is recommended.
6 720 810 590-18.1Wo