3-1 RAS-13GKHP-ES2 / RAS-13GAH-ES2 3-2 RAS-13GKP-ES2 / RAS-13GA-ES2 3-3 RAS-13NKHP-AS2 / RAS-13N2AH-AS2 3-4 RAS-13NKP-AS2 / RAS-13N2A-AS2 SPECIFICATION OF ELECTRICAL PARTS 4-1 Indoor Unit (RAS-13GKHP-ES2, RAS-13NKHP-AS2) 4-2 Outdoor Unit (RAS-13GAH-ES2,RAS-13N2AH-AS2) 4-3 Indoor Unit (RAS-13GKP-ES2,RAS-13NKP-AS2) 4-4 Outdoor Unit (RAS-13GA-ES2,RAS-13N2A-AS2) REFRIGERATION CYCLE DIAGRAM...
Page 3
9-6 Troubleshooting for Remote Control (Including The Indoor P.C. Board) 10. PARTS REPLACEMENT 10-1 Indoor Unit 10-2 Outdoor Unit 11. EXPLODED VIEWS AND PARTS LIST 11-1 Indoor Unit (E-Parts Assy) (For RAS-13GKHP-ES2) 11-2 Indoor Unit (E-Parts Assy) (For RAS-13NKHP-AS2) 11-3 Indoor Unit (E-Parts Assy) (For RAS-13GKP-ES2) 11-4...
Page 5
FILE NO. SVM-06027 Note : 1 • Capacity is based on the following temperature conditions. JIS B8615-1 Condition Temperature Cooling Heating (DB) 27°C 20°C Indoor unit inlet air temperature (WB) 19°C 15°C (DB) 35°C 7°C Outdoor unit inlet air temperature (WB) 24°C 6°C...
FILE NO. SVM-06027 2. CONSTRUCTION VIEWS 2-1. Indoor Unit Front panel Air inlet Air filter Heat exchanger Air outlet Knock out system Knock out system Hanger Connecting pipe (0.43m) Drain hose (0.54m) (Flare ∅6.35) Hanger Connecting pipe (0.33m) (Flare ∅12.7) For stud bolt (∅...
FILE NO. SVM-06027 4. SPECIFICATION OF ELECTRICAL PARTS 4-1. Indoor Unit ( RAS-13GKHP-ES2, RAS-13NKHP-AS2) Parts name Type Specifications ° Fan motor (for indoor) SKF-220-20-4A-1 AC Motor with 150 C thermo fuse ° Thermo sensor (TA-sensor) 10k at 25 C µRM1260V...
FILE NO. SVM-06027 4-3. Indoor Unit (RAS-13GKP-ES2, RAS-13NKP-AS2) Parts name Type Specifications ° Fan motor (for indoor) SKF- 220-20-4A-1 AC Motor with 150 C thermo fuse ° Thermo sensor (TA-sensor) 10k at 25 C TT-10 Transformer Microcontroller unit (IC30) TMP87CM40AN Heat exchanger sensor °...
FILE NO. SVM-06027 7. OPERATION DESCRIPTION 7-1. Outline of Air Conditioner Control 7-1-1. Louver control (1) Vertical air flow louver This is a fixed capacity type air conditioner, which uses Position of veritcal air flow louver is automatically AC motor for an indoor fan. The AC motor drive controlled according to the operation mode.
FILE NO. SVM-06027 7-2. Description of Operation Circuit 7-2-2. Cooling operation ([MODE] button on the remote control is set (1) When turning on the breaker, the operation lamp to the cooling operation.) blinks. This means that the power supply is on. (1) The compressor, 4-way valve, outdoor fan and (2) When pressing [ ] button on the remote control,...
Page 20
FILE NO. SVM-06027 7-2-3. Dry operation 7-2-4. Heating operation *Heat pump model only ([MODE] button on the remote control is set ([MODE] button on the remote control is set to the dry operation.) to the heating operation.) (1) The compressor, 4-way valve, outdoor fan and (1) The compressor, 4-way valve, outdoor fan and operation display on the remote control are operation display on the remote control are...
Page 21
FILE NO. SVM-06027 7-2-5. Automatic operation (3) The indoor heat exchanger restricts revolving speed of the fan motor to prevent a cold draft. The ([MODE] button on the remote control is set upper limit of the revolving speed is shown in to the automatic operation.) Fig.
FILE NO. SVM-06027 7-3. Hi POWER Mode 7-4. High-Temperature Limit Control ([Hi POWER] button on the remote *Heat pump model only control is pressed.) The microcontroller detects the indoor heat exchanger temperature to prevent pressure of a refrigerating cycle When [Hi POWER] button is pressed while the indoor from increasing excessively.
FILE NO. SVM-06027 7-6. Defrost Operation * <In case of C> Heat pump model only (1) The heating operation is performed for at least 90 During the heating operation, the outdoor heat minutes. exchanger temperature goes down and sometimes it is frozen.
FILE NO. SVM-06027 7-7. Current Limit Control *Heat pump model only The microcontroller detects the input current so as to prevent it exceeds a specified value by means of controlling the outdoor fan control as described in (1) and (2). (1) Current limit control (Cooling operation) Control is performed as shown below by detecting the compressor operating current with a current...
FILE NO. SVM-06027 7-8. Auto Restart Function 7-8-1. How to set auto restart function To set the auto restart function, proceed as follows: The indoor unit is equipped with an automatic The power supply to the unit must be on; the function restarting function which allows the unit to restart will not set if the power is off.
FILE NO. SVM-06027 7-8-2. How to cancel auto restart function To cancel auto restart function, proceed as follows: Repeat the setting prodedure: the unit receives the signal and beeps three times. The unit will be required to be turned on with the remote control after the main power supply is turned off.
FILE NO. SVM-06027 7-10. Self-Cleaning function Self-Cleaning function is designed to reduce humidity that causes mold to form inside the air conditioning unit. This advanced, efficient system reduces moisture in the coil. When air conditioner is turned off, the internal fan activates and dries the moisture in the coil for 20 minutes, then it turns off automatically.
FILE NO. SVM-06027 7-11. QUIET Mode 7-12-1. Cooling mode • The fan speed of indoor unit operates automatically, Quiet mode is the system which, control the it relates with the compressor's operation. revolving speed of indoor fan to work constantly at lower than speed L.
FILE NO. SVM-06027 8. INSTALLATION PROCEDURE 8-1. Safety Cautions For general public use Power supply cord of parts of appliance for Outdoor use shall be at least polychloroprene sheathed flexible cord (design H07 RN-F), or cord designation 245 IEC66. CAUTION New Refrigerant Air conditioner Installation •...
Page 30
Also, make sure the equipment is properly earthed. • Appliance shall be installed in accordance with national wiring regulations. If you detect any damage, do not install the unit. Contact your TOSHIBA dealer immediately. CAUTION • Exposure of unit to water or other moisture before installation could result in electric shock.
FILE NO. SVM-06027 8-2. Installation Diagram of Indoor and Outdoor Units For the rear left and left piping Hook Installation plate Wall Insert the cushion between the indoor unit and wall, and tilt the indoor unit for better operation. Shield Do not allow the drain hose pipe to get slack.
FILE NO. SVM-06027 8-3. Installation 8-3-1. Optional installation parts Part Parts name Q'ty Code Refrigerant piping Liquid side : ∅6.35 mm : ∅ each Gas side 12.7 mm Pipe insulating material (polyethylene foam, 6 mm thick) Putty, PVC tapes each <Fixing bolt arrangement of outdoor unit>...
Page 33
FILE NO. SVM-06027 8-3-2. Accessory and installation parts Part Part Part Part name (Q'ty) Part name (Q'ty) Part name (Q'ty) Mounting screw ∅4 x 25 s x 6 Installation plate x 1 Remote control holder x 1 Pan head wood screw Sasa-Zeolite Vitamin C filter x 1 ∅3.1 x 16 s x 2 Wireless remote control x 1...
Page 34
FILE NO. SVM-06027 8-3-3. Installation/Servicing tools <Changes in the product and components> In the case of an air conditioner using R410A, in order to prevent any other refrigerant from being charged accidentally, the service port diameter of the outdoor unit control valve (3 way valve) has been changed. (1/2 UNF 20 threads per inch) •...
FILE NO. SVM-06027 8-4-2. Cutting a hole and mounting installation 8-4. Indoor Unit plate 8-4-1. Installation place <Cutting a hole> • A place which provides the spaces around the When installing the refrigerant pipes from the rear. indoor unit as shown in the above diagram. •...
Page 36
Anchor bolt NOTE • Ensure all wiring is used within its electrical rating. Projection 15 mm or less 5 mm dia. hole RAS-13GKHP-ES2 RAS-13GKP-ES2 Model 7 Mounting RAS-13NKHP-AS2 screw ∅4 x 25s s s s s RAS-13NKP-AS2 Power source 50 Hz, 220 −...
Page 37
FILE NO. SVM-06027 <How to connect the connecting cable> For Cooling Wiring of the connecting cable can be carried out Cord clamp Terminal Terminal block without removing the front panel. cover 1. Remove the air inlet grille. Screw Open the air inlet grille upward and pull it toward Connecting cable you.
Page 38
FILE NO. SVM-06027 8-4-4. Piping and drain hose installation How to fix the drains cap 1) Insert hexagonal wrench (4 mm) in a center <Piping and drain hose forming> head. * Since dewing results in a machine trouble, make sure to insulate both the connecting pipes. (Use polyethylene foam as insulating material.) 4 mm Rear right...
Page 39
FILE NO. SVM-06027 <Left-hand connection with piping> 8-4-5. Indoor unit fixing Bend the connecting pipe so that it is laid within 43 mm 1. Pass the pipe through the hole in the wall, and hook above the wall surface. If the connecting pipe is laid the indoor unit on the installation plate at the upper exceeding 43 mm above the wall surface, the indoor hooks.
FILE NO. SVM-06027 8-4-6. Drainage 8-5. Outdoor Unit 1. Run the drain hose sloped downwards. 8-5-1. Installation place • A place which provides the spaces around the NOTE outdoor unit as shown in the left diagram. • Hole should be made at a slight downward slant on •...
Page 41
FILE NO. SVM-06027 (Unit : N·m) 8-5-2. Refrigerant piping connection 1. Cut the pipe with a pipe cutter. Outer dia. Tightening torque 16 to 18 (1.6 to 1.8 kgf·m) ∅6.35 Roughness Warp Obliquity 90° ∅ 12.70 50 to 62 (5.0 to 6.2 kgf·m) Fig.
Page 42
FILE NO. SVM-06027 8-5-3. Evacuating <Packed valve handling precautions> After the piping has been connected to the indoor unit, • Open the valve stem all the way out; but do not try you can perform the air purge together at once. to open it beyond the stopper.
FILE NO. SVM-06027 8-5-4. Wiring connection 8-6. How to Set Remote Control Selector 1. Remove the valve cover from the outdoor unit. Switch 2. Connect the connecting cable to the terminal as When two indoor units ae installed in seperated rooms, identified with their respective matched numbers on there is no need to change the selector switch.
FILE NO. SVM-06027 2. Set the remote control selector switch with the 8-7. Others remote control 8-7-1. Gas leak test [B] is indicated on the liquid crystal display when setting remote control selector switch to B. [A] is not indicated on the display even if the selector switch is set to A.
FILE NO. SVM-06027 9. TROUBLESHOOTING CHART 9-1. Troubleshooting Procedure 9-2-2. Incorrect cable connection between Indoor and outdoor units Follow the details of 9-2. Basic Check Items. The indoor unit is connected to the outdoor unit with If there is no troub le corresponding to 9-2, check 5 cables (Heat pump model) or 3 cables (Cooling Only whether or not there are faulty parts following model).
FILE NO. SVM-06027 9-3. Primary Judgement 9-3-2. Failure diagnosis The indoor unit diagnoses the operation condition and 9-3-1. Role of indoor unit controller indicates the information of the self-diagnosis with the The indoor unit controller receives the operation lamps on the display panel of the indoor unit. commands from the remote control and executes them.
FILE NO. SVM-06027 9-4. Self-Diagnosis by Remote Control (Check Code) (1) If the lamps are indicated as shown B to G in Table 9-3-1, exchanger the self-diagnosis by the remote control. (2) When the remote control is set to the service mode, the indoor controller diagnoses the operation condition and indicate the information of the self-diagnosis on the display of the remote...
Page 48
FILE NO. SVM-06027 Table 9-4-1 Block level Diagnosis function Judgement and action Check Check Block Symptom Conditioner Condition code code status Indoor Thermo. sensor Indicated Continued 1.Check thermo sensor. P.C. board short/break. when detected operation. 2.If it is OK, check abnormal P.C.
FILE NO. SVM-06027 9-5. Troubleshooting Flowcharts 9-5-1. Power can not be turned on (No operation at all) <Preliminary checks> Operation (1) Is the supply voltage normal? (2) Is the connection to the AC output OK.? Check Items Heat pump Model Main cause Shut off the power supply from AC outlet once and...
Page 50
FILE NO. SVM-06027 Cooling Model Operation Check Items Main cause Shut off the power supply from AC outlet once and Countermeasure turn it on after 5 seconds. Symptom Does the OPERATION lamp blink? Does the power turn on Does the transmission by pushing the [ indicator of remote Remote control is...
Page 51
FILE NO. SVM-06027 9-5-2. Power can not be turned on after replacing indoor P.C. board <Checking Procedure> Connect the AC Power supply Return the wiring of the Does the OPERATION Is it wired as shown power relay is returned to lamp blink? in Figure below? the normal procedure.
Page 52
FILE NO. SVM-06027 Cooling Model Black White Green / Yellow RY01 Indooe Terminal Block CN31 Brown Blue Green / Yellow PC Board 9-5-3. Outdoor unit does not operate Shut off the power supply from AC outlet once and turn it on after 5 seconds. Does the OPERATION lamp blink? See "Power can not be turned on".
Page 53
FILE NO. SVM-06027 9-5-4. Only compressor does not operate Shut off the power supply from AC outlet once and turn it on after 5 seconds. Does the OPERATION lamp blink? See "Power can not be turned on". Does the power turn on by See "Power can not be turned on".
Page 54
FILE NO. SVM-06027 9-5-5. Only outdoor fan does not operate Shut off the power supply from AC outlet once and turn it on after 5 seconds. Does the OPERATION lamp blink? See "Power can not be turned on". Does the power turn on by See "Power can not be turned on".
Page 55
FILE NO. SVM-06027 9-5-6. Only 4-Way valve does not operate (During heating operation) Heat Pump Model Shut off the power supply from AC outlet once and turn it on after 5 seconds. Does the OPERATION lamp blink? See "Power can not be turned on". Does the power turn on by See "Power can not be turned on".
Page 56
FILE NO. SVM-06027 9-5-7. Only the indoor fan does not operate <Check procedure> Heat Pump Model Shut off the power supply once. Turn the power supply. Does the fan stop in Replace the P.C. board. Control P.C. board is defective. no operating status? Start the operation with low fan setting...
Page 57
FILE NO. SVM-06027 Cooling Model Shut off the power supply once. Turn the power supply. Does the fan stop in Replace the P.C. board. Control P.C. board is defective. no operating status? Start the operation with low fan setting in cool operation. Does connecting terminal, connecting Does AC 120V...
FILE NO. SVM-06027 9-6. Troubleshooting for Remote Control (Including the Indoor P.C. Board) There is no been from the indoor unit. Push the [ ] button. The operation lamp of the air conditioner main unit does not light. Does the transmission indicator blink? Reset the remote control by use the tip pencil push...
Page 59
FILE NO. SVM-06027 9-6-1 How to check the P.C. board (2) Inspection procedres 1) When a P.C. board is judged to be defective, (1) Operating precautions check for disconnection, burning, or discolora- 1) When removing the front panel or the P.C. board, tion of the copper foil pattern or this P.C.
FILE NO. SVM-06027 10. PART REPLACEMENT 10-1. Indoor Unit Part name Procedures Remarks Front panel How to remove the front panel 1) Stop the operation of the air conditioner and turn off its main power supply. 2) Pull the air inlet grille toward you to open it and remove the air inlet grille.
Page 61
FILE NO. SVM-06027 Part name Procedures Remarks Heat exchanger 1) Remove the front panel, electrical part and the horizontal louver following procedure 3. 2) Remove the pipe holder at the rear side of main unit. 3) Remove the 2 screws on the heat exchanger at the base bearing.
FILE NO. SVM-06027 10-2. Outdoor Unit Part name Procedures Remarks Cord clamp 2-Screws Ø4 x 16L Common 1) Stop the operation of air-conditioner, and procedure disconnect the power cord from the AC supply. 2) Remove packed valve cover and Electric parts cover.
11-5. Indoor Unit Location Part Location Part Description Description 43T00435 FRONT PANEL ASSY 43T49331 PLATE OF EVA SEAL (RAS-13GKHP-ES2,RAS-13NKHP-AS2) 43T49006 HOLDER FOR PLATE 43T00430 FRONT PANEL ASSY 43T22308 ASM-M-BEARING (RAS-13GKP-ES2,RAS-13NKP-AS2) 43T39301 BASE; BEARING 43T09387 INLET GRILLE ASSY 43T20321 ASSY-CROSS FLOW FAN...