AUTO STOP ·········The air conditioner stops after the set time lapses.
AUTO START ········The air conditioner starts after the set time lapses.
AUTO OFF ············Timer is not active.
<How to operate>
1 Push POWER ON/OFF button.
2 Check if or not the current time is correct.
3 Push the
or
4 Set the timer time using HR and MIN buttons.
Test run
Measure an impedance between the power supply terminal block on
the outdoor unit and ground with a 500V Megger and check that it is
equal to or greater than
1.0M".
1 Turn on the main power to the unit.
TEST RUN
2 Press the
button twice continuously.
(Start this operation from the status of remote controller display
turned off.)
TEST RUN
A
and current operation mode are displayed.
MODE
3 Press the
(
check whether cool air is blown out from the unit.
FAN
4 Press the
button and check whether strong air is blown out
from the unit.
VANE
5 Press the
button and check whether the auto vane operates
properly.
6 Press the ON/OFF button to stop the test run.
Note:
• Point the remote controller towards the indoor unit receiver
while following steps 2 2 to 6 6 .
• It is not possible to run the in FAN, DRY or AUTO mode.