Revision A: •MU-A12YV - can be connected to MCF-A12WV - SPECIFICATION and PERFORMANCE CURVES have been added. TECHNICAL CHANGES MU-A07WV- MU-A07YV- MU-A09WV- MU-A09YV- 1. Outdoor heat exchanger has changed. 2. Outdoor fan motor has changed. (RA6V23-FC RC6V20-AC) MU-A12WV- MU-A12YV- 1. Outdoor heat exchanger has changed. 2.
Page 3
New Specification Current Specification The incompatible refrigerating oil easily separates from Since refrigerant and refrigerating oil are compatible each, refrigerant and is in the upper layer inside the suction muffler. refrigerating oil backs to the compressor through the lower Raising position of the oil back hole enables to back the position oil back hole.
Page 4
2.Refrigerant piping 1 Specifications Use the refrigerant pipes that meet the following specifications. Outside diameter Wall Pipe Insulation material thickness For liquid 6.35 0.8 mm Heat resisting foam plastic 0.8 mm 9.52 For gas Specific gravity 0.045 Thickness 8 mm 0.8 mm 12.7 •...
PART NAMES AND FUNCTIONS OUTDOOR UNIT MU-A07YV - Air inlet (back and side) MU-A09YV - MU-A12YV - Piping Drain hose Air outlet Drain outlet SPECIFICATION MU-A12YV - MU-A12YV - Outdoor model MU-A07YV - MU-A09YV - Indoor unit Indoor unit MSC-A12YV - MCF-A12WV - Single phase Single phase...
NOISE CRITERIA CURVES MU-A12YV- MU-A07YV- SPL(dB LINE FUNCTION FUNCTION SPL(dB LINE MU-A09YV- COOL COOL Test conditions, Test conditions, Cooling :DB35: WB24: Cooling : DB27: WB19: NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 APPROXIMATE APPROXIMATE TERESHOLD OF TERESHOLD OF HEARING FOR HEARING FOR NC-20...
OUTLINES AND DIMENSIONS MU-A07YV - MU-A09YV - MU-A12YV - Unit: mm REQUIRED SPACE OUTDOOR UNIT Air in Air in Drainage 3holes [33 Air out Service panel Liquid refrigerant pipe joint Refrigerant pipe (flared) [6.35 Gas refrigerant pipe joint Refrigerant pipe (flared) [9.52 (MU-A07/A09YV ) [12.7 (MU-A12YV ) WIRING DIAGRAM...
MAX. REFRIGERANT PIPING LENGTH Refrigerant piping Piping size O.D : mm Length of connecting pipe : m Model Max. length : m Outdoor unit Liquid Indoor unit MU-A07YV - 9.52 MU-A09YV - Gas 0 Gas 0.43 6.35 Liquid 0 Liquid 0.5 MU-A12YV - 12.7 MAX.
INDOOR UNIT OUTDOOR UNIT Wet-and dry-bulb Wet-and dry-bulb thermometers thermometers 8-1.CAPACITY AND THE INPUT CURVES 11.0 10.0 8-2.OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT COOL operation Both indoor and outdoor unit are under the same temperature/humidity condition. Relative humidity(%) Dry-bulb temperature Air flow should be set at MAX.
TROUBLESHOOTING MU-A07YV - MU-A09YV - MU-A12YV - 9-1. Cautions on troubleshooting 1. Before troubleshooting, check the following: 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for mis-wiring. 2. Take care the following during servicing. 1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the unit, and then after con- firming the horizontal vane is closed, turn off the breaker and/or disconnect the power plug.
Page 21
9-2. Instruction of troubleshooting MU-A07YV - MU-A09YV - MU-A12YV - Start Indoor unit OPERATION Indoor unit Indoor unit operates. INDICATOR operates. doesn't receive Outdoor unit lamp on the Outdoor unit the signal from doesn't operate indoor unit is doesn't remote controller. normally.
Page 22
9-3. Trouble criterion of main parts MU-A07YV - MU-A09YV - MU-A12YV - Figure Part name Check method and criterion Compressor (MC) Measure the resistance between the terminals with a tester. INNER (Coil wiring temperature –10°C ~ 40°C) PROTECTOR MU-A07/A09YV Normal AUX.
DISASSEMBLY INSTRUCTIONS <"Terminal with lock mechanism" Detaching points> In case of terminal with lock mechanism, detach the terminal as shown below. There are two types ( Refer to (1) and (2)) of the terminal with lock mechanism. The terminal with no lock mechanism can be removed by pulling it out. Check the shape of the terminal and work.
Page 24
OPERATING PROCEDURE PHOTOS 2. Removing the electrical parts Photo 4 (1) Remove the service panel and the cabinet.(Refer to 1.) Compressor (2) Remove the following parts. Screws capacitor • Compressor capacitor (C1) Relay panel • Outdoor fan capacitor (C2) • Terminal block Contractor Terminal block Outdoor fan capacitor...
Page 25
OPERATING PROCEDURE PHOTOS 4. Removing the compressor Photo 6 (1) Remove the cabinet. (Refer to 1.) Suction pipe Discharge pipe (2) Remove the relay panel. (3) Remove the soundproof felt. (4) Remove the terminal cover on the compressor. (5) Disconnect lead wires from the glass terminal of the com- Glass pressor.
PARTS LIST MU-A07YV - MU-A09YV - MU-A12YV - 11-1. OUTDOOR UNIT STRUCTURAL PARTS Part number that is circled is not shown in the illustration. Q'ty/unit Symbol Part No. in Wiring Part name Remarks MU-A09YV- MU-A07YV- MU-A12YV- Diagram E02 832 630 OUTDOOR HEAT EXCHANGER E02 815 232 CABINET...
Page 27
MU-A07YV - MU-A09YV - MU-A12YV - 11-2. OUTDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS Part numbers that are circled are not shown in the illustration. Q'ty/unit Symbol Part No. Part name in Wiring Remarks MU-A07YV- MU-A09YV- MU-A12YV- Diagram E02 665 501 PROPELLER E02 832 301 OUTDOOR FAN MOTOR...
Page 28
HEAD OFFICE: MITSUBISHI DENKI BLDG.,2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN C C Copyright 2003 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD New publication, effective Mar. 2004 Distributed in Mar. 2004. No.OB330 REVISED EDITION-A 6 Specifications subject to change without notice. Distributed in Dec. 2003. No.OB330 6...